Description of parameters
vacon · 57
24-hour support: +358 (0)201 212 575 • Email: [email protected]
5
5.
Description of parameters
5.1
Basic parameters
2.1.1
Grid Nominal Voltage V
ID110
This parameter sets the incoming line voltage for the regenerative drive. Set this
parameter to the nominal line voltage at the installation site. Used also as a reference
point for grid voltage protection functions. Use G2.2.8 Voltage Correction for static
voltage correction.
When transformer parameters are given, this parameter will be voltage reference of grid
when operating in Island and uGrid modes. When transformer rating is different than 1:1
System Rated DC parameter must be given so that AFE operation will work correctly and
MCB is closed at correct voltage level.
2.1.2
Grid Nominal Frequency
Hz
ID1532
Micro Grid and Island mode frequency set point. In Micro Grid mode used as a reference
point for the Base Current reference and drooping. In AFE mode used as a reference
point for frequency protection functions. Use G2.11 FreqDroopOffset for static frequency
adjustment.
+1
%
+2%
+3%
+4%
-1%
-2%
-3%
-4%
50,5 Hz
51,0 Hz
51,5 Hz
52,0 Hz
48,0 Hz
48,5 Hz
49,0 Hz
49,5 Hz
50,0 Hz
L
oad
ing
U
n
-l
o
adi
ng
Droo
ping
Freq.
Change
25%
50%
75%
100%
Related
Load
Figure 10.
2.1.3
System Rated Current A
ID113
The rated current capacity of the supply or the transformer. It can be necessary to set it
if AFE is overdesigned compared to the supply or feeding transformer capacity.
The active current and the reactive current are scaled to this parameter as is the current
cutter level.