46 · vacon
Parameter list
Tel. +358 (0)201 2121 • Fax: +358 (0)201 2121 205
4
4.6
Limit settings
4.6.1
Current limit
Table 22.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.1.1 Current
Limit
0 Varies
A
Varies
107
Total current limit
P2.6.1.2
Short Circuit Level
0
800,1
%
800.0
1620
Disabled above 499.0%
P2.6.1.3
Short Circuit Time
0
5000
ms
0
1515
P2.6.1.4
High Freq. Current
Limit
0 1
0 1517
0 = Enabled (FR)
1 = Disabled (INU)
P2.6.1.5
BiPhase fault
voltage level
0.00 150.00 %
0.00
1518
4.6.2
Active current limit
Table 23.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.2.1
Output Active
Current Limit
0 300 % 300 1290
Generating Active Current
limit in AFE mode to grid.
P2.6.2.2
Input Active Current
Limit
0 300 % 300 1289
Motoring Active Current
limit in AFE mode to DC.
P2.6.2.3 Limit
increase
Rate 0
10000
%/s
100
1502
P2.6.2.4
High Frequency
Power Limit
0.00
100.00
Hz
0.00
1703
0.00 = Not Used.
4.6.3
Frequency limit
Table 24.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.3.1
Line High Trip Limit
0.00
120.00
Hz
75.00
1716
F10 immediately if above
P2.6.3.2
Line Low Trip Limit
0.00
120.00
Hz
25.00
1717
F10 immediately if below
4.6.4
Micro Grid
Table 25.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.4.1
Current limit Min
-300.0
0.0
%
1621
Island and uGrid mode
P2.6.4.2
Current limit Max
0.0
300.0
%
1622
Island and uGrid mode
P2.6.4.3
Max Limit Increase
rate
0 10000
%/s
1502
P2.6.4.4
Current limit Kp
0
1000
1623
P2.6.4.5
Current Limit ti
0
1000
ms
1625
P2.6.4.6
Current Limit Max
Minimum
0.0 10.0 %
1890
P2.6.4.7
Current Limit To
Zero Mode
0 10
1539
0 = No Action
1 = At Stop State