Installation of indoor unit
EDUS281120_a
132
RZR-P, RZQ-P(9)
3P161684-6K
20
English
CAUTION
•
W
hen clamping wiring, use the included clamping material to prevent outside pressure being exerted on the
wiring connections and clamp firmly.
W
hen doing the wiring, make sure the wiring is neat and does not
cause the control box cover to stick up, then close the cover firmly.
•
W
hen attaching the control box cover, make sure you do not pinch any wires.
•
A
fter all the wiring connections are done, fill in any gaps in the through holes with putty or insulation (pro-
cured locally) to prevent small animals and insects from entering the unit from outside. (If they get in, they
could cause short circuits in the control box.)
•
Outside the unit, separate the low voltage wiring (remote controller wire) and high voltage wiring (power
supply, ground, and other power wiring) at least 2in. so that they do not pass through the same place
together. Proximity may cause electrical interference, malfunctions, and breakage.
9-2 Wiring example
WARNING
Install a ground fault circuit interrupter.
The installation of a ground fault circuit interrupter is imperative for the prevention of electric shocks and fire
accidents.
•
Fit the power supply wiring of each unit with a disconnect switch and a maximum overcurrent protective
device as shown in the drawing.
COMPLETE SYSTEM EXAMPLE
Remote controller wiring
Sealing pad (Small) (13)
Putty or thermal insulation material
(procured locally)
Wiring through-holes
Pro
c
e
ssi
ng method of w
i
r
i
ng thro
u
gh-hole
s
F
i
g
.
28
Power supply
Main
switch
Outdoor unit
Power supply wire
Transmission wire
Disconnect switch
Maximum overcurrent
protective device
Indoor unit
Remote controller
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...