Installation of indoor unit
EDUS281120_a
202
RZR-P, RZQ-P(9)
3PN14093-12A
16
English
Table 4
CAUTION
Keep in mind that a shortage of airflow quantity or water leakage
will result because the air conditioner will be operated outside
the rated range of airflow quantity if the external static pressure
is wrongly set.
3. Filter sign settings
• The remote controller is provided with an LCD that tells
the time of air filter cleaning.
• If the air conditioner is used in places with excessive dust,
change the “SECOND CODE NO.” as shown in Table 5.
The “SECOND CODE NO.” is set to 01 (standard) at fac-
tory set.
Table 5
* Select “No display” under conditions in which the cleaning
display is not required, such as the time of regular mainte-
nance.
12. TEST RUN
Refer to the installation manual of the outdoor unit.
• The operation lamp of the remote controller will flash when a
malfunction occurs. Check the malfunction code on the liquid
crystal display to identify the point of trouble. An explanation
of malfunction codes and the corresponding trouble is pro-
vided in the installation manual attached to the outdoor unit
or the service manual.
If any of the items in Table 7 is displayed, there may be a
problem with the wiring or power supply, so check the wiring
again.
Table 6
Table 7
CAUTION
If interior finish work is continuing on completion of the test run
of the air conditioner, explain the customer not to operate the air
conditioner until the interior finish work is completed for the pro-
tection of the air conditioner.
Otherwise, substances that will be generated from interior finish
work materials, such as paint and adhesive agents, may con-
taminate the air conditioner.
External Static
Pressure
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
0.20 inWG
13 (23)
06
02
0.24 inWG
03
0.28 inWG
04
0.32 inWG
05
0.36 inWG
06
0.40 inWG
07
0.44 inWG
08
0.48 inWG
09
0.52 inWG
10
0.56 inWG
11
0.60 inWG
12
0.64 inWG
13
0.72 inWG
14
0.80 inWG
15
Dirt
Time for
display
Mode No.
FIRST
CODE
NO.
SECOND
CODE
NO.
Standard
Approxi-
mately 2500
hours
10 (20)
0
01
Excessive
dust
Approxi-
mately 1250
hours
02
No display (*)
3
Remote controller display
Contents
“A8” is lit up
Error in power supply voltage to
indoor unit.
“C1” is lit up
Fan driver PCB of indoor unit
↔
indoor control PCB transmission
error.
“C6” is lit up
Improper combination of fan driver
PCB of indoor unit or setting failure
in control PCB type.
“U3” is lit up
Test run of outdoor unit has not
been finished.
Remote controller display
Contents
“
” is lit up
• There is a short circuit at the
FORCED OFF terminals (T1, T2)
“U4” is lit up
“UH” is lit up
• The power supply on the outdoor
unit is off.
• The outdoor unit has not been
wired for power supply.
• Incorrect wiring for the transmis-
sion and / or the FORCED OFF
wiring.
No display
• The power supply on the indoor
unit is off.
• The indoor unit has not been
wired for power supply.
• Incorrect wiring for the remote
controller, the transmission and /
or the FORCED OFF.
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...