Connect the piping. (See “5.REFRIGERANT PIPING WORK” and Fig. 10)
(8)
Secure with
vinyl tape.
Seal with putty corkin
g
material.
Drain hose
Transmission wirin
g
and remote controller
wirin
g
Fig. 10
A
A
arrow view
Refri
g
erant pipin
g
Transmission wirin
g
and
remote controller wirin
g
Wrap the insulatin
g
tape overlappin
g
at least half the width with each wrap.
Wrap the insulatin
g
tape all the way to the L-shaped bend.
Refri
g
erant pipin
g
Conduit
Seal the piping through-hole with putty corking material.
•
Push on both bottom edges of the indoor unit using both hands and hook the tab on the back of
(9)
the indoor unit onto the installation panel (1). (Refer to Fig. 9)
At this time remove the buffering material placed in step (6).
•
Make sure power supply wiring, transmission wiring, ground wiring and remote controller wiring are
•
not caught inside the indoor unit.
When screwing in the indoor unit
Installation panel
(accessory) (1)
Refri
g
erant pipin
g
Insulatin
g
tape
(accessory) (4)
M4 × 12L
(accessory) (6)
Fig. 11
Remove the front grill
E
.
•
(Refer to Fig. 7)
Secure the indoor unit to the installation panel (1) with the securing
•
screws (6).
(Refer to Fig. 11)
REFRIGERANT PIPING WORK
5.
〈
For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.
〉
〈
Execute heat insulation work completely on both sides of the gas piping and the liquid piping.
Otherwise, a water leakage can result sometimes.
〉
"ESURETOUSEINSULATIONTHATISDESIGNEDFORUSEWITH(6!#SYSTEMS
〈
Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed
86ºF or RH80 %, reinforce the refrigerant insulation. (13/16” or thicker) Condensation may form on
the surface of the insulating material.
〉
〈
Before refrigerant piping work, check which type of refrigerant is used. Proper operation is not
possible if the types of refrigerant are not the same.
〉
DANGER
Refrigerant gas may produce toxic gas if it comes in contact with fi re such as from a fan, heater, stove or
•
cooking device. Exposure to this gas could result in severe injury or death.
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...