CAUTION
Drain piping connections
•
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the
sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.
ELECTRIC WIRING WORK
7.
GENERAL INSTRUCTIONS
7-1
All fi eld supplied parts and materials and electric works must conform to local codes.
•
Use copper wire only.
•
For electric wiring work, refer to also “WIRING DIAGRAM” attached to the unit.
•
For remote controller wiring details, refer to the installation manual attached to the remote controller.
•
All wiring must be performed by an authorized electrician.
•
This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and be sure the
•
terminal block wiring to the outdoor unit and B
RANCH
S
ELECTOR
unit is properly matched. If wiring and piping
outdoor unit and indoor unit are mismatched, the system may cause a malfunction.
A circuit breaker capable of shutting down power supply to the entire system must be installed.
•
Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected
•
to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
Be sure to ground the air conditioner.
•
DANGER
Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding
•
could cause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas
leak could result in an explosion which could lead to severe injury or death.
ELECTRICAL CHARACTERISTICS
7-2
Units
Power supply
Fan motor
Model
Hz
Volts
Voltage range
MCA
MFA
W
FLA
FAQ18PVJU
60
208-230
Max. 253
Min. 187
0.4
15
43
0.3
FAQ24PVJU
0.6
15
43
0.5
MCA: Min. Circuit Amps (A);
MFA: Max. Fuse Amps (A)
W: Fan Motor Rated Output (W);
FLA:
Full Load Amps (A)
SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE
7-3
Model
Power supply wiring
Remote controller wiring
Transmission wirin
G
F
USEBREAKER
Size
Wire
Size
FAQ18PVJU
15A
Size must comply
with local codes.
NONSHIELDEDCOPPER
2
CONDUCTORSTRANDED
!7
G18-
FAQ24PVJU
Allowable length of transmission wiring and remote controller wiring are as follows.
•
(1) Outdoor unit - Indoor unit:Max.3280ft. (Total wiring length: 6560ft.)
(2) Indoor unit - Remote controller:Max.1640ft.
Insulated thickness: 1/16” or more.
•
./4%%ITHERAFUSEORABREAKERISACCEPTABLE
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...