ELECTRIC WIRING WORK
9-1
GENERAL INSTRUCTIONS
• All field supplied parts and materials and electric works must
conform to local codes.
• Use copper wire only.
• For electric wiring work, refer to also “Wiring diagram”
attached to the control box cover.
• For remote controller wiring details, refer to the installation
manual attached to the remote controller.
• All wiring must be performed by an authorized electrician.
• A circuit breaker capable of shutting down power supply to
the entire system must be installed.
• Refer to the installation manual attached to the outdoor unit
for the size of power supply wiring connected to the outdoor
unit, the capacity of the ground fault circuit interrupter and
switch, and wiring instructions.
• Be sure to ground the air conditioner.
• Do not connect the ground wiring to gas and water pipes,
lightning rods, or telephone ground wires.
• Gas pipes : might cause explosions or fire if gas leaks.
• Water pipes : no grounding effect if hard vinyl piping is
used.
• Telephone ground wires or lightning rods : might cause
abnormally high electric potential in the ground during
lighting storms.
9-2
ELECTRICAL CHARACTERISTICS
MCA: Minimum Circuit Ampacity (A)
MOP: Maximum Overcurrent Protective Device (A)
kW:
Fan Motor Rated Output (kW)
FLA: Full Load Ampacity (A)
9-3
SPECIFICATIONS FOR FIELD SUPPLIED
FUSE
" 2 % ! + % 2
AND WIRE
Allowable length of transmission wirings and remote controller
wiring are as follows.
(1) Outdoor unit – Indoor unit:
Max. 3280 ft (Total wiring length: 6560 ft)
(2) Indoor unit – Remote controller:
Max. 1640 ft
NOTE
3HOWSONLYINCASEOFPROTECTEDPIPES5SE(2.&IN
CASEOFNOPROTECTION
6INYLCORDWITHSHEATHORCABLE)NSULATEDTHICKNESS
INORMORE
7)2).'%8!-0,%!.$(/74/3%4
4(%2%-/4%#/.42/,,%2
#/..%#4).'0/7%23500,9'2/5.$
2%-/4%#/.42/,,%2!.$42!.3-)33)/.
7)2).'
2EMOVETHECONTROLBOXCOVERASSHOWNBELOWANDCONNECT
EACHWIRE
2EMOVETHECONTROLBOXCOVER
-ODEL
0OWERSUPPLY
&ANMOTOR
(Z
6OLTS 6OLTAGERANGE -#! -/0
+7
&,!
&"106*5
6
6
-AX6
-IN6
&"106*5
&"106*5
&"106*5
&"106*5
./4%%ITHERAFUSEORABREAKERISACCEPTABLE
Model
Power supply wiring
Remote controller wiring
Transmission wiring
fuse
BREAKER
S
ize
Wire
S
ize
FBQ18PVJU
15A
S
ize must
comply
with local
codes.
S
TRANDED
NONSHIELDED
CONDUCTOR
AWG18-
FBQ24PVJU
FBQ30PVJU
FBQ36PVJU
FBQ42PVJU
Screw
(3 portions)
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...