EDUS281120_a
Installation of indoor unit
RZR-P, RZQ-P(9)
147
C: 3PN06240-12Q
11
English
L
1
POWER SUPPLY
L
2
power supply
How to connect power supply
terminal block (2P)
Control box
Transmission
terminal block (6P)
Power supply
te
r
minal block (2P)
Remote controller wire
and transmission wire
Refer to Fig. 27
Ground terminal
Power supply wire
Gas pipe
Liquid pipe
Drain pipe
Conduit
Corkin
g
or Putty
Resin bush (10)
Control box
lid secu
r
in
g
screw (2pcs.)
Control box lid
Insulatin
g
tube (11)
Clamp (4)
Fig. 26
Fastener
Clamp (4)
Clamp (4)
Ground wire
After securin
g
the
cramp material
to the bracket,
cut off any extra
material.
Remote controller wire and
transmission wire
Fastener
Power supply wire
Fig. 27
P
1 P2 F1 F2 T1 T2
REMOTE
CNTRL
FORCED
OFF
TRANSMISSION
WIRING
Clamp (4)
Remote controller wire
Transmission
terminal block (6P)
Transmission wire
Insulating
tube (11)
1 in.
Fig. 28
In the insulating tube (11), it can let the remote controller wire
•
and transmission wire pass to 2.
WARNING
Never connect power supply wiring to the terminal block for
•
remote controller wiring as this could damage the entire system.
Use only specifi ed wire and connect wires to the terminal
•
tightly. Be careful wires do not place external stress on ter-
minals. Keep wires in neat order so as to not obstruct other
equipment. Make sure that the electric box lid fi ts tightly.
Incomplete connections could result in overheating and, in
worse case, result in electric shock or fi re.
NOTE
1. Use round crimp-style terminals for connecting wires to the
power supply terminal block.
If unavailable, observe the following points when wiring.
Do not connect wires of different gauge to the same
•
power supply terminal.
(Looseness in the connection may cause overheating.)
Use the specifi ed electric wire. Connect the wire securely to
•
the terminal. Lock the wire down without applying excessive
force to the terminal. (Tightening torque: 0.97 ft lbf ±10%)
Electric wire
Round crimp-style terminal
Attach insulation sleeve
Connect wires of the
same
g
au
g
e to both side.
2. Tightening torque for the terminal screws.
Use the correct screwdriver for tightening the terminal
•
screws. If the blade of screwdriver is too small, the head
of the screw might be damaged, and the screw will not be
properly tightened.
If the terminal screws are tightened too hard, screws
•
might be damaged.
Refer to the table below for the tightening torque of the
•
terminal screws.
Table 4
Terminal
Size
Tightening torque
(ft-lbf)
Transmission terminal block (6P)
M3.5
0.58 – 0.72
Power supply terminal block (2P)
M4
0.87 – 1.06
Ground terminal
M4
0.87 – 1.06
3. Do not connect wires of different gauge to the same ground
terminal. Looseness in the connection may deteriorate pro-
tection.
4. Outside of the unit, keep transmission wire at least 5 in.
away from power supply wire. The equipment may malfunc-
tion if subjected to electrical (external) noise.
5. For remote controller wire, refer to the “INSTALLATION
MANUAL OF REMOTE CONTROLLER” attached to the
remote controller.
WIRING EXAMPLE
9-2
Fit the power supply wire of each unit with a switch and fuse
•
as shown in the drawing.
COMPLETE SYSTEM EXAMPLE
Power supply wire
Transmission wire
Switch
Fuse
Power supply
Main
switch
Remote controller
Indoor unit
Outdoor unit
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...