Installation of indoor unit
EDUS281120_a
160
RZR-P, RZQ-P(9)
C: 3PN06240-2H
10
• Keep in mind that it will become the cause of getting drain
pipe blocked if water collects on drain pipe.
8
.
ELECTRIC WIRING WORK
8
-1 GENERAL INSTRUCTIONS
• All field supplied parts and materials and electric works must
conform to local codes.
• Use copper wire only.
• For electric wiring work, refer to also
“
Wiring diagram label
”
attached to the control box lid.
• For remote controller wiring details, refer to the installation
manual attached to the remote controller.
• All wires must be performed by an authorized electrician.
• An
GROUND
leakage circuit breaker capable of shutting down
power supply to the entire system must be installed.
• Refer to the installation manual attached to the outdoor unit
for the size of power supply wiring connected to the outdoor
unit, the capacity of the circuit breaker and switch, and wiring
instructions.
• Be sure to ground the air conditioner.
DANGER
• Do not ground units to water pipes, telephone wires or light-
ning rods because incomplete grounding could cause a
severe shock hazard resulting in severe injury or death, and
to gas pipes because a gas leak could result in an explosion
CAUTION
• Even if the control box lid is removed, pull the remote control-
ler wire, transmission wire and the power supply wire inside
the unit using conduits for each, so that the wires do not come
into contact with the opening section of the metal casing.
• Pass conduits through the wall and secure along with the
refrigerant pipe in order to prevent external pressure being
applied to transmission wire and power supply wire.
• To avoid short circuits in the electric parts box, be sure to apply
the sealing material or putty (not included) to the wiring hole to
prevent the infiltration of water, insects or other small creatures.
• Arrange the wires and fix a lid firmly so that the lid does not
float during wiring work.
• Do not clamp remote controller wire and transmission wire
together with power supply wire. Doing so may cause mal-
function.
• Remote controller wire, transmission wire and power supply
wire should be located at least 5 in. from other electric wires.
Not following this guideline may result in malfunction due to
WHICHCOULDLEADTOSEVEREINJURYORDEATH
%,%#42)#!,#(!2!#4%2)34)#3
-#!-IN#IRCUIT!MPS!
-&!-AX&USE!MPS!
7&AN-OTOR2ATED/UTPUT7 &,!&ULL,OAD!MPS!
30%#)&)#!4)/.3&/2&)%,$3500,)%$&53%3
!.$7)2%3
!LLOWABLELENGTHOFTRANSMISSIONWIREBETWEENINDOOROUTDOOR
UNITSANDBETWEENTHEINDOORUNITANDTHEREMOTECONTROLLERWIRE
AREASFOLLOWS
/UTDOORUNITn)NDOORUNIT-AXFT
)NDOORUNITn2EMOTECONTROLLER-AXFT
7)2).'%8!-0,%!.$(/74/3%4
4(%2%-/4%#/.42/,,%2
(/74/#/..%#47)2%3
./4%%ITHERAFUSEORABREAKERISACCEPTABLE
ELECTRICALNOISE
-ETHODOFWIRINGPOWERSUPPLYUNITSANDCONNECT
INGREMOTECONTROLLERWIRING2EFERTO&IG
s !TTACHINGTHERESINBUSH
!TTACHTHERESINBUSH FORREMOTECONTROLLERWIRING
s )NSTALLATIONOFCONDUIT
)NSERTTHECONDUITFORPOWERSUPPLYWIREINTHECONDUITHOLE
ANDFIXITWITHTHELOCKNUT
s 0OWERSUPPLYWIRE
(OLDINGTHECONTROLBOXLIDLOOSENTHESECURINGSCREWS
REMOVETHECONTROLBOXLIDMATCHUPTHEPHASESONTHEPOWER
SUPPLYTERMINALBLOCKINSIDE0 ANDMAKETHECONNECTIONS
!FTERTHISISDONEUSETHEATTACHEDCLAMP TOBINDWIRE
BETWEENUNITSTOTHEANCHORPOINT
2EFERTO&IG
s 2EMOTECONTROLLERWIREANDTRANSMISSIONWIRE
(OLDINGTHECONTROLBOXLIDLOOSENTHESECURINGSCREWS
REMOVETHECONTROLBOXLID
4HREADTHEREMOTECONTROLLERWIREANDTRANSMISSIONWIRE
THROUGHTHEINSULATINGTUBE ANDSECUREWITHTHECLAMP
ANDCUTOFFTHEINSULATINGTUBE TOSUITABLELENGTH0ULL
THEWIRESINSIDETHROUGHRESINBUSHANDCONNECTTHEWIRESTO
THETRANSMISSIONTERMINALBLOCK0 INSIDETHECONTROLBOX
!FTERCONNECTINGUSETHECLAMP TOBINDTHEREMOTECON
TROLLERWIRETOGETHERWITHTHETRANSMISSIONWIRETOTHEANCHOR
2EFERTO&IG
5NITS
0OWERSUPPLY &ANMOTOR
-ODEL
(Z
6OLTS
6OLTAGE
RANGE
-#! -&!
7
&,!
&(1-6*5
6
-AX6
-IN6
&(1-6*5
&(1-6*5
&(1-6*5
-ODEL
0OWERSUPPLYWIRING
2EMOTECONTROLLERWIRING
4RANSMISSIONWIRING
&IELDFUSES
3IZE
7IRE
3IZE
&(1-6*5
!
7IRESIZEMUSTCONDUCTOR
COMPLYWITH
LOCALCODES
3TRANDEDNON
SHIELDEDCOPPER
!7'
&(1-6*5
&(1-6*5
&(1-6*5
Resin bush (10)
Lock nut
Conduit
Conduit hole
Fig. 25
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...