![background image](http://html1.mh-extra.com/html/daikin/skyair-rzq-p-series/skyair-rzq-p-series_engineering-data_2459074121.webp)
Installation of indoor unit
EDUS281120_a
120
RZR-P, RZQ-P(9)
3P161684-6K
8
English
䡵
Installation is possible when ceiling opening dimensions is as follows
•
When installing the unit within the frame for fixing false ceiling.
NOTE
•
Installation is possible with a ceiling dimension of 35-7/8in. (marked with *). However, to achieve a ceiling-
panel overlapping dimension of 13/16in., the spacing between the ceiling and the unit should be 1-3/8in. or
less. If the spacing between ceiling and the unit is over 1-3/8in., attach ceiling material to
part or
recover the ceiling.
(2) Make the ceiling opening needed for installation where applicable. (For existing ceilings)
•
R
efer to the paper pattern for installation (5) for ceiling opening dimensions.
•
Create the ceiling opening required for installation. From the side of the opening to the casing outlet,
implement the refrigerant and drain piping and wiring for remote controller (unnecessary for wireless
type) and indoor-outdoor unit casing outlet.
R
efer to “6.
R
EF
R
IGE
R
ANT PIPING WO
R
K”, “7. D
R
AIN
PIPING WO
R
K” and “8. ELECT
R
IC WI
R
ING WO
R
K”.
•
After making an opening in the ceiling, it may be necessary to reinforce ceiling beams to keep the ceiling
level and to prevent it from vibrating. Consult the builder for details.
(
3
) Install the suspension bolts.
(Use either a M8~M10 size bolt or the equivalent)
Use a hole-in anchor for existing ceilings, and a
sunken insert, sunken anchor or other field sup-
plied parts for new ceilings to reinforce the ceiling
to bear the weight of the unit. Adjust clearance
(2-4in.) from the ceiling before proceeding
further.
NOTE
•
All the above parts are field supplied.
(Dimension inside fr
ame)
33-1/16
35-7/8
35-7/8
(Dimension inside frame)
33-1/16
Fig. 6
33-7/8
(Opening dimension inside
the flame for ceiling)
Frame
≥
13/16
33-7/8 – *35-7/8
(Ceiling-panel
overlapping dimension)
False
ceiling
(Ceiling opening dimension)
≥
13/16
Fig. 7
(Unit: in.)
Ceiling material
1-3/8
Fig. 8
≥
1-3/8
≥
(Unit: in.)
2-4
Ceiling slab
Suspension bolt
Long nut or turn-buckle
Anchor
False ceiling
<installation example>
Fig. 9
(Unit: in.)
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...