Installation of indoor unit
EDUS281120_a
146
RZR-P, RZQ-P(9)
C: 3PN06240-12Q
10
English
Keep in mind that it will become the cause of getting drain
•
pipe blocked if water collects on drain pipe.
ELECTRIC WIRING WORK
8.
GENERAL INSTRUCTIONS
8-1
All fi eld supplied parts and materials and electric works must
•
conform to local codes.
Use copper wire only.
•
For electric wiring work, refer to also “Wiring diagram label”
•
attached to the control box lid.
For remote controller wiring details, refer to the installation
•
manual attached to the remote controller.
All wires must be performed by an authorized electrician.
•
An earth leakage circuit breaker capable of shutting down
•
power supply to the entire system must be installed.
Refer to the installation manual attached to the outdoor unit
•
for the size of power supply wiring connected to the outdoor
unit, the capacity of the circuit breaker and switch, and wiring
instructions.
Be sure to ground the air conditioner.
•
DANGER
Do not ground units to water pipes, telephone wires or
•
lightning rods because incomplete grounding could cause a
severe shock hazard resulting in severe injury or death, and
to gas pipes because a gas leak could result in an explosion
which could lead to severe injury or death.
ELECTRICAL CHARACTERISTICS
8-2
Units
Power supply
Fan motor
Model
Hz
Volts
Voltage
range
MCA
MFA
W
FLA
FHQ18PVJU
60 208-230V
Max. 253V
Min. 187V
1.3
15
130
1.0
FHQ24PVJU
1.3
15
130
1.0
FHQ30PVJU
1.3
15
130
1.0
MCA : Min. Circuit Amps (A);
MFA : Max. Fuse Amps (A)
W: Fan Motor Rated Output (W); FLA : Full Load Amps (A)
SPECIFICATIONS FOR FIELD SUPPLIED FUSES
8-3
AND WIRES
Model
Power supply wiring
Remote controller wiring
Transmission wiring
f
USEBREAKER
3IZE
7IRE
3IZE
&(106*5
!
7IRESIZEMUST
COMPLYWITH
LOCALCODES
CONDUCTOR
NONSHIELDED
!7'
&(106*5
&(106*5
!LLOWABLELENGTHOFTRANSMISSIONWIREBETWEENINDOOROUTDOOR
UNITSANDBETWEENTHEINDOORUNITANDTHEREMOTECONTROLLERWIRE
AREASFOLLOWS
/UTDOORUNIT)NDOORUNIT-AXFT
)NDOORUNIT2EMOTECONTROLLER-AXFT
./4%%ITHERAFUSEORABREAKERISACCEPTABLE
WIRING EXAMPLE AND HOW TO SET
9.
THE REMOTE CONTROLLER
HOW TO CONNECT WIRES
9-1
CAUTION
Even if the control box lid is removed, pull the remote control-
•
ler wire, transmission wire and the power supply wire inside
the unit using conduits for each, so that the wires do not come
into contact with the opening section of the metal casing.
Pass conduits through the wall and secure along with the
•
refrigerant pipe in order to prevent external pressure being
applied to transmission wire and power supply wire.
To avoid short circuits in the electric parts box, be sure to apply
•
the sealing material or putty (not included) to the wiring hole to
prevent the infi ltration of water, insects or other small creatures.
Arrange the wires and fi x a lid fi rmly so that the lid does not
•
fl oat during wiring work.
Do not clamp remote controller wire and transmission wire
•
together with power supply wire. Doing so may cause mal-
function.
Remote controller wire, transmission wire and power supply
•
wire should be located at least 5 in. from other electric wires.
Not following this guideline may result in malfunction due to
electrical noise.
<Method of wiring power supply, units and connect-
ing remote controller wiring> (Refer to Fig. 26)
Attaching the resin bush
•
Attach the resin bush (10) for remote controller wiring.
Installation of conduit
•
Insert the conduit for power supply wire in the conduit hole,
and fi x it with the lock nut.
Resin bush (10)
Lock nut
Conduit
Conduit hole
Fig. 25
Power supply wire
•
Holding the control box lid, loosen the 2 securing screws,
remove the control box lid, match up the phases on the power
supply terminal block inside (2P), and make the connections.
After this is done, use the attached clamp (4) to bind wire
between units to the anchor point.
(Refer to Fig. 27)
Remote controller wire and transmission wire
•
Holding the control box lid, loosen the 2 securing screws,
remove the control box lid.
Thread the remote controller wire and transmission wire
through the insulating tube (11) and secure with the clamp
(4), and cut off the insulating tube (11) to suitable length. Pull
the wires inside through resin bush and connect the wires to
the transmission terminal block (6P) inside the control box.
After connecting, use the clamp (4) to bind the remote con-
troller wire together with the transmission wire to the anchor.
(Refer to Fig. 26, 27, 28)
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...