EDUS281120_a
Installation of indoor unit
RZR-P, RZQ-P(9)
177
3PN07521-2C
12
English
CAUTION
CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
•
“Do not use fl ux when brazing refrigerant piping. Therefore, use the phosphor copper brazing fi lter metal
(BCuP) which does not require fl ux.”
(Flux has an extremely negative effect on refrigerant piping systems. For instance, if chlorine based fl ux
is used, it will cause pipe corrosion. If the fl ux contains fl uorine, it will damage the refrigerant oil.)
When brazing the refrigerant piping, only begin brazing after having carried out nitrogen substitution
•
(NOTE 1) or while inserting nitrogen into the refrigerant piping (NOTE 2). Once this is done, connect the
indoor unit with a fl ared or a fl anged connection.
DANGER
Use of oxygen may cause an explosion resulting in serious injury or death. Only use nitrogen gas.
•
NOTE
Refer to the “Manual for Multi Installation for Buildings” for directions on how to carry out nitrogen
1.
substitution. (Inquire with your dealer.)
Nitrogen should be set to 2.9 psi with a pressure-reducing valve if brazing while inserting nitrogen into
2.
the piping.
(Refer to Fig. 14)
Refri
g
erant pipin
g
Part to be
brazed
Tapin
g
Pressure-reducin
g
valve
hands valve
Nitro
g
en
Fig. 14
Nitro
g
en
After checking for gas leaks, be sure to insulate the pipe connections using the supplementary piping
•
insulation tubing and insulating tape (4). The insulating tape (4) should be wrapped from the L-shaped
bend all the way to the end inside the unit.
(Refer to Fig. 15)
Insulatin
g
tubin
g
tape
Insulatin
g
tubin
g
tape
Local pipin
g
Indoor unit pipin
g
Indoor unit pipin
g
insulation tubin
g
Clampin
g
material lar
g
e
(accessory) (5)
Insulatin
g
tape (accessory) (4)
L-shaped
bend
Start wrappin
g
See “ 4.INDOOR UNIT
INSTALLATION ”
Indoor unit pipin
g
insulation tubin
g
Insulatin
g
tubin
g
tape
Insulation tubin
g
seam
Attach the insulation tubin
g
tape so that there are no
g
aps
in the insulation tubin
g
seam.
Fig. 15
CAUTION
Be sure to insulate any fi eld piping all the way to the piping connection inside the unit. Any exposed piping
•
may cause condensate or burns if touched.
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...