EDUS281120_a
Installation of indoor unit
RZR-P, RZQ-P(9)
135
3P161684-6K
English
23
9-4 Computerized control (forced off and on/off operation)
(1) Wire specifications and how to perform wiring
•
Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller.
(2) Actuation
•
The following table explains FORCED OFF and ON/OFF OPERATIONS in response to Input A.
(3) How to select FORCED OFF and ON/OFF OPERATION
•
Turn the power on and then use the remote controller to select operation.
9-5 Centralized control
•
For centralized control, it is necessary to designate the group No. For details, refer to the manual of each
optional controllers for centralized control.
10. INSTALLATION OF THE DECORATION PANEL
<If performing a test run without attaching the decoration panel, read “11. FIELD SETTING” and “12. TEST
RUN” first.>
Refer to the installation manual attached to the decoration panel.
After installing the decoration panel, ensure that there is no space between the unit body and decoration panel.
Note:
Since the electric insulation sheet stacked to the control box cover gets sandwiched between the unit body and
decoration panel, when closing the cover, slip the insulation sheet between them first and then attach the cover
to the control box.
Wire specification
CONDUCTORSTRANDEDNONSHIELDEDCOPPER06#ORVINYLJAKCET
Gauge
AWG18 -
Length
Max. 328ft.
External terminal
Contact that can ensure the minimum applicable load of 15 V DC, 1 mA.
FORCED OFF
ON/OFF OPERATION
Input “ON” stops operation (impossible by remote controllers.) Input OFF
→
ON turns ON unit.
Input OFF enables control by remote controller.
Input ON
→
OFF turns OFF unit.
F2
T1
T2
FO
R
CED
OFF
I
n
put
A
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...