EDUS281120_a
Installation of indoor unit
RZR-P, RZQ-P(9)
199
3PN14093-12A
English
13
(4) Put the control box cover, and wrap the wire sealing mate-
rial (Small) (10) around the conduit so as to block the wire
through holes.
CAUTION
• After all the wiring connections are done, fill in any gaps in the
through holes with putty or insulation (procured locally) to pre-
vent small animals and insects from entering the unit from
outside. (If any do get in, they could cause short circuits in the
control box.)
[Precautions for Power Supply Wiring]
• Connect round crimp-style terminals provided with insulation
sleeves to the terminal block for power supply.
Be sure to follow the instructions provided below if the spec-
ified terminals cannot be used.
Otherwise, abnormal heat may be generated as a result
of the loosening of the wires.
• If stranded wires are used, do not solder the front end of the
wires.
• Connect proper wires securely and fix the wires so that exter-
nal force will not be imposed on the terminals.
• Use an appropriate screwdriver to tighten the terminal
screws. The screw heads may be damaged if the screwdriver
is too small and the terminal screws will not be tightened
properly.
• Do not tighten the terminal screws excessively, or otherwise
the screw heads may be damaged.
•
R
efer to the table below for the required tightening torque val-
ues of the terminal screws.
10-2 WIRING EXAMPLE
WARNING
Install a ground fault circuit interrupter.
The installation of a ground fault circuit interrupter is imperative
for the prevention of electric shocks and fire accidents.
COMPLETE SYSTEM EXAMPLE
1. When using 1 remote controller (Normal operation)
Tightening torque (lbf·ft)
Terminal block for remote controller
and transmission wires
0.58 - 0.72
Terminal block for power supply
Ground wiring
0.87 - 1.06
Wire through holes
Electric wire
Round crimp-style terminal
Attach insulation sleeve
Connect the wires
evenly.
Do not connect a
wire to the single
side only.
Do not connect
wires different
from each other in
diameter.
Power supply
Main
switch
Outdoor unit
Power supply wire
Transmission wire
Disconnect switch
Maximum overcurrent
protective device
Indoor unit
Remote controller
L
1
L
2
IN/D OUT/D
F1 F2 F1 F2
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
Control box
Power Supply
208/230V
1 ~ 60Hz
Outdoor unit
Indoor unit
Remote
controller
L
1
L
2
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...