Installation of outdoor unit
EDUS281120_a
212
RZR-P, RZQ-P(9)
3P281953-2A
English
10
Pipe size
Tightening
torque (ft·lbf)
Flare dimension
A (in.)
Flare shape (in.)
φ
3/8”
24.1 - 29.4
0.504 - 0.520
A
45°± 2°
90°± 2°
R0.016
~0.031
φ
5/8”
45.6 - 55.6
0.760 - 0.776
Ester oil or ether oil
If you are obliged to install the unit without a torque wrench,
•
you may follow the installation method mentioned below.
After the work is fi nished, make sure to check that there is
no gas leak.
When you keep on tightening the fl are nut with a spanner,
•
there is a point where the tightening torque suddenly in-
creases.
From that position, further tighten the fl are nut the angle
shown below.
Pipe size
Tightening angle
(Guideline)
Recommended arm
length of tool (in.)
φ
3/8”
60°~90°
Approx. 7 7/8
φ
5/8”
30°~60°
Approx. 11 13/16
Disposal requirements
Dismantling of the unit, treatment of the refrigerant, oil and
eventual other parts should be comply the relevant local and
national regulations.
Refrigerant piping work procedure
6-4
The fi eld piping can be connected in three directions.
Piping cover
Screw for
front panel
Screw for piping
cover (front)
Front
panel
Lateral
direction
Front direction
Downward
direction
When connecting the piping downward, remove the knock-
out hole by making four holes in the middle on the each side
of the knockout hole with a drill.
Field piping
Bottom frame
Knockout hole
Drill
Slit
Middle on the side
Slit
Then cut out the corner of the bottom frame along the slits (in
two positions) by using a hacksaw.
After removing the parts, it is recommended to apply repair
paint on the edges, to prevent rusting.
Cautions on connecting the connection piping
When it is expected that water condensed in the stop valve
•
will reach the indoor unit through the gap between the heat
insulating material and the piping (for example, when the
outdoor unit is installed in a higher position than the indoor
unit), take proper action such as caulking the connection
area.
[Measures to prevent invasion of small creatures and litter]
Block all gaps in the piping penetration areas with putty or
•
heat insulating material (arranged in the local fi eld) as
shown in the fi gure below.
(If small creatures such as insects or litter enter the outdoor
unit, a short-circuit may be caused inside the control box.)
Putty or heat
insulating material
(arranged in local field)
Heat insulation of piping
6-5
Make sure to insulate the fi eld piping (on both the liquid line
•
and gas line) and refrigerant branching kit.
(If they are not insulated, water leakage may be caused.)
"ESURETOUSEDINSULATIONTHATISDESIGNEDFORUSEWITH
(6!#SYSTEMS
Reinforce the refrigerant piping according to the installation
•
environment. If it is not reinforced, condensate may form on
the surface of the insulation.
WARNING
Make sure to insulate the fi eld piping up to the piping con-
•
nection area inside the unit. If the piping is exposed, dew
condensation and burn by contact may be caused.
Airtight test and vacuum drying
6-6
The unit has been checked for leaks by the manufacturer.
Confi rm that the valves are fi rmly closed before airtight test or
vacuumdrying.
To prevent entry of any impurities and insure suffi cient pres-
sure resistance, always use the special tools dedicated for
R410A.
Perform the following inspections securely after the
piping work.
Airtight test
•
- Make sure to use nitrogen gas. (For the
service port position, refer to the fi gure in “
Stop valve
operation method
”.)
[Procedure] Pressurize the air conditioner from the liquid
pipe and gas pipe up to 450 psi (Make sure not to exceed
450 psi). When the pressure does not drop for 24 hours, the
piping work shall be accepted.
If the pressure drops, check for leakage positions. (Confi rm
that there is no leakage, then release nitrogen.)
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...