Installation of outdoor unit
RZR-P, RZQ-P(9)
207
3P281953-2A
5
English
40 or more
Branch switch
and overcurrent
protective device
Indoor remote
controller
60 or more
60 or more
40 or more
Branch switch
and overcurrent
protective device
60 or more
Indoor unit
(in.)
DANGER
Do not install unit in an area where fl ammable materials are
•
present due to risk of explosion resulting in serious injury or
death.
Refrigerant is heavier than air and replaces oxygen. A
•
massive leak could lead to oxygen depletion , especially in
basements, and an asphyxiation hazard could occur leading
to serious injury or death.
Installation place (unit: inch)
〈
Cautions on continuous installation
〉
The connection piping outlet direction in the continuous
•
installation shown in the fi gures below is frontward or down-
ward.
When routing the piping rearward, secure space of 10 in. or
•
more on the right side of the outdoor unit. (The unit of nu-
meric values below is “inch”.)
Make some space for wiring with conduit and servicing
•
between the units.
(A) When an obstruction is present on the air inlet side
When the upward area is open
•
When one outdoor unit is installed individually
(1)
When an obstruction is present only on the air inlet
•
side
4 or more
When an obstruction is present on the both sides
•
4 or more
4 or more
4 or more
When two or more outdoor units are installed side
(2)
by side
When an obstruction is present on the both sides
•
40 or more
12 or more
8 or more
When an obstruction is present also in the upward area
•
When one outdoor unit is installed individually
(1)
When an obstruction is present also on the air inlet
•
side
20 or less
40 or more
4 or more
When an obstruction is present also on the air inlet
•
side and both sides
6 or more
6 or more
20 or less
6 or more
40 or more
When two or more outdoor units are installed side
(2)
by side
When an obstruction is present also on the air inlet
•
side and both sides
20 or less
8 or more
40 or more
12 or more
40 or more
Summary of Contents for SkyAir RZQ-P Series
Page 1: ...Cooling Only 60Hz Heat Pump 60Hz RZR P RZQ P 9 series EDUS281120_a AMERICAS ...
Page 31: ...Dimensions and service space EDUS281120_a 30 RZR P RZQ P 9 BRC2A71 Unit in 3D047341 ...
Page 33: ...Dimensions and service space EDUS281120_a 32 RZR P RZQ P 9 BRC7E818 for FAQ 3D049736 Unit in ...
Page 34: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 33 BRC4C82 for FBQ 3D049611 Unit in ...
Page 38: ...EDUS281120_a Dimensions and service space RZR P RZQ P 9 37 3D064213A ...
Page 39: ...Dimensions and service space EDUS281120_a 38 RZR P RZQ P 9 3D064213A ...
Page 41: ...Dimensions and service space EDUS281120_a 40 RZR P RZQ P 9 3D047381B ...
Page 47: ...Wiring diagrams EDUS281120_a 46 RZR P RZQ P 9 FAQ18PVJU FAQ24PVJU 3D046039D ...
Page 61: ...Safety devices list EDUS281120_a 60 RZR P RZQ P 9 8 3 FAQ FAQ18PVJU FAQ24PVJU 4D047085B ...
Page 91: ...Capacity tables EDUS281120_a 90 RZR P RZQ P 9 RZR36PVJU RZR42PVJU 3D071685 ...
Page 92: ...EDUS281120_a Capacity tables RZR P RZQ P 9 91 RZQ36PVJU9 RZQ42PVJU9 C 3D047383B ...
Page 101: ...Sound Levels Reference EDUS281120_a 100 RZR P RZQ P 9 FBQ18PVJU FBQ24PVJU FBQ30PVJU FBQ36PVJU ...
Page 102: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 101 FBQ42PVJU ...
Page 104: ...EDUS281120_a Sound Levels Reference RZR P RZQ P 9 103 RZQ42PVJU9 RZR42PVJU 4D072769 ...