Specifications
Si12-411A
32
Specifications
50Hz 220-230-240V / 60Hz 220-230V
Notes:
1. The data are based on the conditions shown in the table below.
Model
4MKD90BVM
Cooling Capacity
kW
—
Power Consumption
W
—
Running Current
A
—
Casing Color
Pale Ivory
Compressor
Type
Hermetically Sealed Swing Type
Model
2YC45ZXD
Motor Output
W
1,380
Refrigerant Oil
Model
SUNISO 4GSD.I.
Charge
L
0.75
Refrigerant
Type
R22
Charge
kg
3.1
Air Flow Rates
m³/min
H
48.5
L
42
cfm
H
1,400
L
1,212
Fan
Type
Propeller
Motor Output
W
51
Running Current
A
H: 0.44 / L: 0.34
Power Consumption
W
H: 60 / L: 41
Starting Current
A
12.1
Dimensions (H×W×D)
mm
908×900×320
Packaged Dimensions (H×W×D)
mm
942×926×394
Weight
kg
66
Gross Weight
kg
77
Operation Sound
dBA
48
Piping Connection
Liquid
mm
φ
6.4×2,
φ
9.5×2
Gas
mm
φ
12.7×1,
φ
15.9×3
Drain
mm
φ
25.0
Heat Insulation
Both Liquid and Gas Pipes
No. of Wiring Connection
3 for Power Supply, 4 for Interunit Wiring
Max. Piping Length
m
70 (for Total of Each Room)
m
25 (for One Room)
Amount of Additional Charge
g/m
Chargeless
Max. Installation Height Difference
m
15 (between Indoor Unit and Outdoor Unit)
m
7.5 (between Indoor Units)
Drawing No.
3D039670#1
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling
Piping Length
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB
5.0m
Summary of Contents for FTKE25BVM
Page 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A...
Page 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v...
Page 7: ...Si12 411A vi Table of Contents...
Page 67: ...Specifications Si12 411A 56 Specifications...
Page 173: ...Instruction Si12 411A 162 System Configuration...
Page 227: ...Check Si12 411A 216 Service Diagnosis...
Page 295: ...Si12 411A iv Index...
Page 298: ...Si12 411A Printed in Singapore 03 2005 AK COS...