Si12-411A
Check
Service Diagnosis
213
6.1.11
Capacitor Voltage Check
Check No.12
Before this checking, be sure to check the main circuit for short-circuit.
Checking the capacitor voltage
z
With the circuit breaker still on, measure the voltage according to the drawing of the model in
question. Be careful never to touch any live parts.
6.1.12
Power Transistor Check
Check No.13
Checking the power transistor
z
Never touch any live parts for at least 10 minutes after turning off the circuit breaker.
z
If unavoidably necessary to touch a live part, make sure the power transistor's supply
voltage is below 50 V using the tester.
z
For the UVW, make measurements at the Faston terminal on the board or the relay
connector.
Fan motor
lead wire
Solenoid valve
coil lead wire
(Room A)
Solenoid valve
coil lead wire
(Room B)
Solenoid valve
coil lead wire
(Room C)
Solenoid valve
lead wire
Thermistor
lead wire
(liquid pipe)
Thermistor
lead wire
(gas pipe)
Thermistor
lead wire
OL
lead wire
Reactor
lead wire
Compressor
lead wire
TB2
>PS<
TB3
P2
N1
590
592
593
580
520
521
522
540
(Q0366)
Use the tester
in the DC range.
Tester's negative terminal
Power transistor
(+)
UVW
Power transistor
(–)
UVW
Tester's positive terminal
UVW
Power transistor
(+)
UVW
Power transistor
(–)
Normal resistance
Several kohms to several Mohms
Abnormal resistance
0 or
∞
Summary of Contents for FTKE25BVM
Page 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A...
Page 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v...
Page 7: ...Si12 411A vi Table of Contents...
Page 67: ...Specifications Si12 411A 56 Specifications...
Page 173: ...Instruction Si12 411A 162 System Configuration...
Page 227: ...Check Si12 411A 216 Service Diagnosis...
Page 295: ...Si12 411A iv Index...
Page 298: ...Si12 411A Printed in Singapore 03 2005 AK COS...