Outdoor Unit (80 / 90 Class)
Si12-411A
234
Removal Procedure
1.6
Removal of
Electronic Expansion Valve
and
Thermistor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1
Remove each wire
harness.
Place the thermistor so that
its end comes up to the end
of the presser spring.
Be careful not to lose the
presser spring for the
discharge pipe thermistor.
2
Take off the putty, and
remove each
thermistor.
S90:
Outdoor air thermistor (Blue)
Heat exchanger thermistor
(Gray)
Discharge pipe thermistor
(Black)
S92: Gas pipe thermistor
Room A (Black)
Room B (Gray)
Room C (Brown)
Room D (Red)
S93: Liquid pipe thermistor
Room A (Black)
Room B (Gray)
Room C (Yellow)
Room D (Blue)
3
Remove the electronic
expansion valve coil.