Si12-411A
Troubleshooting
Service Diagnosis
169
5. Troubleshooting
5.1
Indoor Units
- : Not used for troubleshooting
∗
: Varies depending on the cases.
Indication on
the remote
controller
Description of The Fault
Details of fault
(Refer to the
indicated
page.)
00
Indoor unit in normal condition (Conduct a diagnosis of the outdoor
unit.)
—
A1
Indoor unit PCB abnormality
A5
Freeze-up protection control or high pressure control (heat pump
model only)
A6
Fan motor or related
abnormality
AC motor (Wall : 20~35, Duct, Floor / Ceiling)
DC motor (Wall : 50~71, Floor)
C4
Heat exchanger thermistor or related abnormality
C7
Shutter drive motor / shutter limit switch abnormality
C9
Room temperature thermistor abnormality
U4
Signal transmission error (between indoor and outdoor units)
UA
Unspecified voltage (between indoor and outdoor units)