Troubleshooting
Si12-411A
184
Service Diagnosis
5.12 Compressor Lock
Remote
Controller
Display
E6
Outdoor Unit LED
Display
A
5
1
1
2
4
3
4
4
1
Method of
Malfunction
Detection
A compressor lock is detected by checking the compressor running condition through the
position detection circuit.
Malfunction
Decision
Conditions
The position detection circuit detects a compressor frequency of below 10 Hz for 20 seconds
or a frequency of above 160 Hz.
40 seconds after the compressor has started, the position detection circuit detects a
compressor frequency of above 180 Hz.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 5 minutes (normal)
Supposed
Causes
Compressor locked
Troubleshooting
Turn off the power. Disconnect the
harnesses U, V and W.
∗
Inverter checker
Part No.: 1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
Replace the compressor.
Check the electronic
expansion valve.
Replace it as required.
Replace the compressor.
(R2842)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
YES
System shut
down after errors repeated
several times?
NO
NO
Normal?
YES
Emergency stop
without compressor
running?
Check with the inverter checker (
∗
).
Turn off the power and reconnect
the harnesses. Turn on the power
again and get the system restarted.
Summary of Contents for FTKE25BVM
Page 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A...
Page 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v...
Page 7: ...Si12 411A vi Table of Contents...
Page 67: ...Specifications Si12 411A 56 Specifications...
Page 173: ...Instruction Si12 411A 162 System Configuration...
Page 227: ...Check Si12 411A 216 Service Diagnosis...
Page 295: ...Si12 411A iv Index...
Page 298: ...Si12 411A Printed in Singapore 03 2005 AK COS...