Outdoor Unit (50 / 52 / 58 / 68 / 75 Class)
Si12-411A
256
Removal Procedure
2.9
Removal of
Compressor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1
Remove the terminal
cover.
2
Disconnect the
compressor lead wire.
As precaution, keep the contents
in memorandum.
3
Remove the 2 sheets of
putty.
Be careful to avoid burning
the compressor terminals or
the nameplate.
4
There is one nut fixing
the compressor.
Remove the nut with an
open-end spanner.
Make sure there is no
refrigerant gas left inside
the refrigerant pipes
before starting the job.
When heating up the
brazed parts, make sure
to carry out the N2
replacement.
Warning
The compressor's refrigerating
machine oil may catch fire.
Have wet cloth at hand for
quickly putting out the fire.
Warning
If refrigerant gas leaks during
the job, ventilate the room.
(Bear in mind that if the
refrigerant gas is exposed to
open flames, noxious gas may
be generated.)
Caution
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the gas
welding rod.
1
Disconnect the brazed
part (a) at discharge
side of the compressor.
2
Disconnect the brazed
part (b) at suction side
of the compressor.
Summary of Contents for FTKE25BVM
Page 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A...
Page 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v...
Page 7: ...Si12 411A vi Table of Contents...
Page 67: ...Specifications Si12 411A 56 Specifications...
Page 173: ...Instruction Si12 411A 162 System Configuration...
Page 227: ...Check Si12 411A 216 Service Diagnosis...
Page 295: ...Si12 411A iv Index...
Page 298: ...Si12 411A Printed in Singapore 03 2005 AK COS...