Control Specification
Si12-411A
104
Function and Control
Detail
Judgment by Input Current
When an output frequency is exceeds 55 Hz and the input current is less than specified value,
the adjustment is made for insufficient gas.
Judgment by Discharge Pipe Temperature
When discharge pipe temperature is 20°C higher than target value and the electronic expansion
value opening is 450 plus (max.), the adjustment is made for insufficient gas.
3.13.4
Preventing Indoor Freezing
During cooling, if the heat exchanger temperature in the operation stopped room becomes
below the specified temperature for the specified time, open the electronic expansion valve in
the operation stopped room as specified, and carry out the fully closed operation. After this, if
freezing abnormality occurs more than specified time, the system shall be down as the system
abnormality.
3.14
Forced Operation Mode
Outline
Forced operating mode includes functions such as; forced cooling, forced heating, incorrect
wiring, incorrect piping check.
Operating mode must be selected by operating the forced operation switch.
Detail
Forced Cooling, Forced Heating (Only for Heat Pump Model)
Item
Forced Cooling
Forced Heating
Forced operation
allowing conditions
1) The indoor unit is not abnormal, but
the indoor unit which is not in the
freezing prohibiting zone is present in
more than 1 room.
1) The indoor unit is not abnormal.
The indoor unit which is not in the
peak-cut prohibited zone is present in
more than 1 room.
2) The outdoor unit is not abnormal
and not in the 3-minute stand-by
mode.
←
3) The operating mode of the outdoor
unit is the stop mode.
←
4) The slide selection switch of the
forced operation is the cooling mode.
The forced operation is allowed when
the above “and” conditions are met.
4) The slide selection switch of the
forced operation is the heating mode.
The forced operation is allowed when
the above “and” conditions are met.
Starting / adjustment If the forced operation switch is
pressed as the above conditions are
met.
←
1) Determine
operating room
All rooms
1 room operation, with the room that
can enable operation and its NO is the
smallest (A>B>C>D). Other rooms
operation must be stopped.
2) Command
frequency
2YC32: 52 Hz
2YC45: 42 Hz
2YC32: 44 Hz
(Outdoor air temp:0°C)
2YC45: 37 Hz
(Outdoor air temp:0°C)
3) Electronic
expansion valve
opening
Depending on the capacity of the
operating indoor unit.
←
4) Outdoor unit
adjustment
Compressor is in operation
←
5) Indoor unit
adjustment
Transmit the command of forced
draft to the indoor unit
←
End
1) When the forced operation switch is
pressed again.
←
2) The operation is to end
automatically after 30 min.
←
Others
The protect functions are prior to all
others in the forced operation.
←
Summary of Contents for FTKE25BVM
Page 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A...
Page 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v...
Page 7: ...Si12 411A vi Table of Contents...
Page 67: ...Specifications Si12 411A 56 Specifications...
Page 173: ...Instruction Si12 411A 162 System Configuration...
Page 227: ...Check Si12 411A 216 Service Diagnosis...
Page 295: ...Si12 411A iv Index...
Page 298: ...Si12 411A Printed in Singapore 03 2005 AK COS...