Si12-411A
Troubleshooting
Service Diagnosis
191
5.17
Position Sensor Abnormality
Remote
Controller
Display
H6
Outdoor Unit LED
Display
A
5
1
4
2
4
3
1
4
1
Method of
Malfunction
Detection
A compressor startup failure is detected by checking the compressor running condition through
the position detection circuit.
Malfunction
Decision
Conditions
The compressor fails to start in about 15 seconds after the compressor run command signal
is sent.
Clearing condition: Continuous run for about 5 minutes (normal)
The system will be shut down if the error occurs 16 times.
Supposed
Causes
Compressor relay cable disconnected
Compressor itself defective
Outdoor unit PCB defective
Stop valve closed
Input voltage out of specification
Troubleshooting
Check No.13
Refer to P.213
Replace the outdoor unit
PCB, outdoor unit fan.
Replace the outdoor unit
PCB.
Reconnect as specified.
∗
Inverter checker
Part No.: 1225477
Correct the power supply or
replace the outdoor unit
PCB.
Replace the compressor.
(R2847)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Normal
NO
NO
NO
YES
YES
NO
YES
Any LED off?
DC380±30V?
Electricals
or compressor harnesses
connected as
specified?
Check the electrolytic capacitor
voltage.
Check with the inverter checker (
∗
).
Turn off the power. Disconnect the
harnesses U, V and W.
C
heck No.
13
Check for short-circuit.
Summary of Contents for FTKE25BVM
Page 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A...
Page 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v...
Page 7: ...Si12 411A vi Table of Contents...
Page 67: ...Specifications Si12 411A 56 Specifications...
Page 173: ...Instruction Si12 411A 162 System Configuration...
Page 227: ...Check Si12 411A 216 Service Diagnosis...
Page 295: ...Si12 411A iv Index...
Page 298: ...Si12 411A Printed in Singapore 03 2005 AK COS...