96
CTC GSi 600
Room temp. reduced, Night red °C
-2 (0...-30)
Room temp. reduced, Holiday °C
-2 (0...-30)
The menus are displayed if room sensors are installed
for the heating circuit. The number of degrees by which
the room temperature should be lowered during remote-
controlled night reduction and during holidays can be
set here. Night reduction can also be set periodically;
the temperature decrease is then entered in the weekly
program.
Prim. flow reduced, Night red °C
-3 (0...-30)
Prim. flow reduced, Holiday °C
-3 (0...-30)
The menus are displayed if room sensors are not is
installed for the heating circuit. The number of degrees
by which the primary flow temperature for the heating
circuit should be lowered during remote-controlled night
reduction and during holidays can be set here. Night
reduction can also be set periodically; the temperature
decrease is then entered in the weekly program.
Alarm room temp °C
5 (-40...40)
If the room temperature is too low (according to the set
value), the message "Alarm, low room temp." will be
displayed.
This menu bar is displayed if the room sensor is
connected and defined.
SmartGrid Low price °C
1 (Off, 1...5 )
Setting to increase inclination adjustment at energy price
"Low price", via SmartGrid.
Both SmartGrid A and SmartGrid B must be defined in
the remote control menu for this menu to be displayed.
Read more in the "Installer/Define/Remote Control/
SmartGrid A/B" chapter.
SmartGrid Overcapacity °C
2 (Off, 1...5)
Setting to increase inclination adjustment at energy price
"Overcapacity", via SmartGrid.
Both SmartGrid A and SmartGrid B must be defined
with a remote control input for this menu to be
displayed.
Read more in the "Installer/Define/Remote Control/
SmartGrid A/B" chapter.
Max time heating (min)
20 (10-120)
This is the maximum time (minutes) during which the
heat pump charges the heating circuit if needed in the
hot water tank.
Charge pump %
90 (20-100)
Setting for charge pump (G11) speed (percent) when
charging the heating circuit.
Example
As a rule, a “Primary flow reduced” reduced value of
3 to 4 °C is equivalent to a reduction of approximately
1 °C in room temperature in a normal system.
i
If room sensors are installed,
the "Room temp lowered..."
menu is displayed. If there are no
room sensors, the "Primary flow
reduced..." menu is displayed.
Summary of Contents for GSi 600 Series
Page 33: ...33 CTC GSi 600 B15 B12 B11 B2 G2 G2 Y2 6 1 17 Schematic diagram passive cooling alt 3 ...
Page 64: ...8 22 HP cooling module schematic diagram 3x400V A5 ...
Page 65: ...8 23 HP cooling module schematic diagram 1x230V 3x230V A5 ...
Page 67: ...M GF B25 B26 Y21 B5 G20 B24 B23 B27 B28 G11 G5 B102 B18 ...
Page 131: ...131 CTC GSi 600 ...
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......