6.1.7
Expansion tank pre-pressure
The pre-pressure in the expansion tank is calculated according to the height
(H) between the highest-positioned radiator and the expansion tank. The
pre-pressure must be checked/set before the system is fi lled with water.
The system pressure must be set 0.3 bar higher than the pre-pressure in
the expansion tank. For example, a pre-pressure of 1.0 bar (5 mvp) means a
maximum permitted height difference of 10 m.
The table assumes installation with the expansion tank
included in the CTC Installation Kit GSi accessory.