34
CTC GSi 600
M
M
MP
MP
B31
Y11
Y31
G30
B30
F2
B47
01
Y41
F3
G31
B7
G32
Y11
6.1.18
Solar heat (accessory)
Solar heat is connected to the system through an external heat source tank
(EHS-tank).
The number of solar panels which can be connected depends on the volume of
water in the product/tanks to which the solar panels are to be connected.
System 1
System 1 is a system structure with solar heat going directly to an external heat
source tank (EHS-tank).
Charging conditions (main conditions, factory settings)
Charging starts when B31 is 7°C warmer than B47.
Charging stops when there is a difference of 3°C between B31/B30 or when the
charge temperature is reached.
The external heat source tank (01) may also have a solar coil; this means that
the heat exchanger (F2), pump (G32) or non-return valve (Y11) is not required.
Schematic diagram only The installation engineer fi ts expansion tank, safety valves, bleeders, etc. and sizes the
system.