127
CTC GSi 600
Current monitor
The heat pump has an integrated current monitor. If the system is fitted with
a current sensor, the property’s main fuses are continuously monitored to
ensure they are not overloaded. If this should happen, electric stages are
disconnected from the heat pump. The heat pump may be restricted where
high heating requirement levels are combined with, for example, single-
phase engine heaters, cookers, washing machines or tumble dryers. This
may result in inadequate heating or DHW temperatures. If the heat pump is
limited, "High current, elpower redu (X A)" appears in text form in the display.
Consult an electrician to determine whether the fuse size is correct or the
three phases in the house are evenly loaded.
Ground loop
Faults can occur in the cooling unit if the ground loop has not been installed
correctly, if it has not been bled sufficiently, if it contains too little antifreeze or
is not designed to an adequate size. Poor or insufficient circulation can result
in the heat pump triggering an alarm in the case of low evaporation. If the
temperature difference between the ingoing and outgoing temperature is too
large, the product triggers an alarm and "Low brine flow" is displayed. The
probable cause is that there is still air in the brine circuit. Bleed thoroughly,
which may in some cases take up to a day. Also check the ground loop.
See also the section entitled “Connecting the brine system”. Reset the “Low
evaporation” alarm on the display. Where a malfunction repeatedly occurs,
call in a technician to investigate and rectify the fault.
If the text "Low brine temp" is displayed, the ground loop may not be
large enough or there may be a fault with the sensor. Check the brine
circuit temperature in the “Current operation data” menu. If the incoming
temperature falls below -5 °C during operation, call in a technician to inspect
the brine circuit.
Air problems
If you hear a rasping sound from the heat pump, check that it is properly
bled. Top up with water where required, so that the correct pressure is
achieved. If this noise recurs, call a technician to check the cause.
Unusual noise when shutting off DHW
In some cases, unusual noises may be produced by the cold water, pipe
work and heat pump due to the jolts which occur when the flow is quickly
interrupted. There is no fault with the product, but the noise may occur
when older types of instant closing mixers are used. More recent types are
often fitted with a soft-closing mechanism. If an unusual sound comes from
hard-closing dishwasher and washing machines, this can be remedied using
a shock arrestor. A shock arrestor can also be an alternative to soft-closing
water taps.
i
Don’t forget that the
radiators may also
need bleeding.
If heating is uneven, perform a check (if room sensor installed):
• That the placement of the room sensors is appropriate for the house.
• That the radiator thermostats don’t interfere with the room sensor.
• That no other heat sources/cold sources interfere with the room
sensor.
Summary of Contents for GSi 600 Series
Page 33: ...33 CTC GSi 600 B15 B12 B11 B2 G2 G2 Y2 6 1 17 Schematic diagram passive cooling alt 3 ...
Page 64: ...8 22 HP cooling module schematic diagram 3x400V A5 ...
Page 65: ...8 23 HP cooling module schematic diagram 1x230V 3x230V A5 ...
Page 67: ...M GF B25 B26 Y21 B5 G20 B24 B23 B27 B28 G11 G5 B102 B18 ...
Page 131: ...131 CTC GSi 600 ...
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......