103
CTC GSi 600
12.9.5 Settings External heat source
(EHS)
Charge start °C
70
This is the minimum temperature required in the external
heat source tank (B47) for the mixing valve to open and
emit heat to the system.
Stop diff
°C
5
Temperature difference before charging stops from the
additional heating source.
SmartGrid block cap.
No (No/Yes)
Electric operation prioritised. The shunt on the EHS tank
is closed to accumulate heat energy.
Read more in the "Installer/Define/Remote control/
SmartGrid" menu.
12.9.6 Settings Diff thermostat
function
The diff thermostat function is used if you want to
transfer heat from a tank with the sensor (B46) to a tank
with the sensor (B47).
The function compares the temperatures in the tanks
and when it is warmer in the first tank (B46), charging
starts to the second tank (B47).
However, this function cannot be combined with the
same function in a solar heating system (when e.g.
an EcoTank is connected). This is because the same
outlets and sensors are used for both functions.
Charge start diff temp °C
7 (3...30)
Here you can set the temperature difference determining
when charging to the EHS tank is started. The
temperature must be this many degrees warmer than
the EHS-tank for charging to start.
Charge stop diff temp °C
3 (2...20)
Here you can set the temperature difference determining
when charging to the EHS tank is stopped. When
the temperature difference falls below this set value,
charging stops.
Charge temperature °C
60 (10...95)
Setting for the maximum permitted temperature in the
EHS tank. Charging stops once the set temperature has
been reached.
Menu: "Installer/Settings/External Heat Source".
Menu: "Installer/Settings/Diff Thermostat Function".
HC2 Mixing valve close
120 (Off/1...300)
The time in seconds to position the mixing valve at 50%.
This is done to prevent flow problems when charging
DHW.
This menu is displayed if heating circuit 2 is defined.
Summary of Contents for GSi 600 Series
Page 33: ...33 CTC GSi 600 B15 B12 B11 B2 G2 G2 Y2 6 1 17 Schematic diagram passive cooling alt 3 ...
Page 64: ...8 22 HP cooling module schematic diagram 3x400V A5 ...
Page 65: ...8 23 HP cooling module schematic diagram 1x230V 3x230V A5 ...
Page 67: ...M GF B25 B26 Y21 B5 G20 B24 B23 B27 B28 G11 G5 B102 B18 ...
Page 131: ...131 CTC GSi 600 ...
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......