30
CTC GSi 600
M
B46
B47
Y11
G46
B7
M
M
B50
G51
Y50
6.1.13
Diff thermostat function
The diff thermostat function is used if you want to transfer heat from a tank
with the sensor (B46) to a tank with the sensor (B47).
The function compares the temperatures in the tanks and, when it is warmer
in the fi rst tank (B46), charging starts to the second tank (B47).
NB: For certain heat sources, e.g. solid fuel boilers, automatic chargers are
recommended, among other things to counteract condensation in the fi re
box.
However, this function cannot be combined with solar system 2 with
EcoTank. This is because the same circulation pump (G46) is used.
“Operation data/Diff thermostat function” displays the information “Status
(On/Off).
i
Ensure a high
fl ow on the pump
(G46) so that a
low temperature
difference of approx.
5-10 °C is achieved
over the EHS tank
during charging.
6.1.14
Pool (accessory)
A pool can be connected to the system using a 3-way valve
(Y50). A heat exchanger should be fi tted to separate the
liquids.
When the pool is heated, the 3-way valve (Y50) changes
direction and the pool pump (G51) starts.
The electric heater is never used to heat the pool.
When a constant fl ow is desired in the pool water, the
pool pump (G51) is connected with a separate supply and
constant voltage.
The expansion card accessory is required to connect pool
heating to your heating circuit.
Summary of Contents for GSi 600 Series
Page 33: ...33 CTC GSi 600 B15 B12 B11 B2 G2 G2 Y2 6 1 17 Schematic diagram passive cooling alt 3 ...
Page 64: ...8 22 HP cooling module schematic diagram 3x400V A5 ...
Page 65: ...8 23 HP cooling module schematic diagram 1x230V 3x230V A5 ...
Page 67: ...M GF B25 B26 Y21 B5 G20 B24 B23 B27 B28 G11 G5 B102 B18 ...
Page 131: ...131 CTC GSi 600 ...
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......