110
CTC GSi 600
12.10.1.2 Remote control functions
The "Installer/Define/Remote Control" menu defines
Inputs for current remote control functions:
• terminal blocks K22, K23, K24, K25.
• wireless accessories in the SmartControl series
(Channel 1A, 1B, 2A, 2B, 3A, 3B and so on up to
7B).
• BMS digital input 0-7. Specify a value 0-255. The
value must be set again within half an hour for the
setting to persist.
Ethernet
(Modbus TCP/Off)
For information about Modbus TCP Port settings, refer
to the "Communication" section in the "Installer/Settings"
chapter.
HC* Night reduction
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
The "Night Reduction" function can be used to, for
example, lower the indoor temperature during the night or
during working hours.
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer / Define/Heating Circuit" menu:
• configure the normal mode for the external control
signal (Normally Open (NO)/Normally Closed (NC))
in the "HC Night reduction ext. config." row.
The weekly program can be set in the "Heating/Cooling"
menu. For more information, refer to the "Night Reduction
Temperature" section in the "Heating/Cooling" chapter.
HC* Heating mode
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
Switching between heating season and summer season
can take place at a specific outdoor temperature (Auto) or
heating can be either always "On" or "Off".
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer / Define/Heating Circuit" menu:
• configure the normal mode for the external control
signal (Normally Open (NO)/Normally Closed (NC))
in the "HC Heating mode ext. config." row.
In the "Installer /Settings/Heating Circuit" menu:
• set "Remote Control Mode" ("On", "Off" or "Auto")
in the "Heating mode, ext." row.
• Access function scheduling from the "Heat mode,
schedule" row.
For more information, refer to the "Heating Circuit" section
in the "Installer/Settings" chapter.
Also refer to the "Your home’s heating settings" chapter.
Part of the "Installer / Define/Remote Control" menu.
"Input" and "Weekly Program" are defined here.
Menu: "Installer/Settings/Heating Circuit". The remote control
mode for the heating circuit is set on menu bar "Heating mode,
ext". Access the weekly program from the menu bar "Heating
mode, schedule".
*CTC GSi can control up to 2 heating circuits.
Summary of Contents for GSi 600 Series
Page 33: ...33 CTC GSi 600 B15 B12 B11 B2 G2 G2 Y2 6 1 17 Schematic diagram passive cooling alt 3 ...
Page 64: ...8 22 HP cooling module schematic diagram 3x400V A5 ...
Page 65: ...8 23 HP cooling module schematic diagram 1x230V 3x230V A5 ...
Page 67: ...M GF B25 B26 Y21 B5 G20 B24 B23 B27 B28 G11 G5 B102 B18 ...
Page 131: ...131 CTC GSi 600 ...
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......