User Manual – Rev B
FCS Series II
TVF 103 Tests – Revision F
TVF103
Voltage Phase Difference - Rev F
Condition
Duration (s)
A
A = 0, B = 116, C = 240
1800
B
A = 0, B = 124, C = 240
1800
TVF 104 Tests - Revision F
TVF104
Voltage Modulation - Rev B through F
Condition
Duration (s)
Run at 400, Repeat at 360, 600 and 800 Hz
A
Vmod F = 1.0 Hz, V = 0.375 Vrms
1800
B
Vmod F = 1.7 Hz, V = 0.375 Vrms
1800
C
Vmod F = 10 Hz, V = 2.5 Vrms
1800
D
Vmod F = 25 Hz, V = 2.5 Vrms
1800
E
Vmod F = 70 Hz, V = 0.375 Vrms
1800
F
Vmod F = 100 Hz, V = 0.375 Vrms
1800
G
Vmod F = 200 Hz, V = 0.375 Vrms
1800
TVF 10
R
5 Tests – evision F
TVF105
Frequency Modulation Rev F
Condition
Duration (s)
Run at 400, Repeat at 362, 600 and 798 Hz
A
Hz
1800
Fmod F = 1 Hz/sec, Fmod Amp = 4 Hz± 2
B
Hz
1800
Fmod F = 5 Hz/sec, Fmod Amp = 4 Hz± 2
C
± 2 Hz
1800
Fmod F = 10 Hz/sec, Fmod Amp = 4 Hz
D
Fmod F = 25 Hz/sec, Fmod Amp = 4 Hz± 2 Hz
1800
E
Fmod F = 100 Hz/sec, Fmod Amp = 4 Hz± 2 Hz
1800