3.4.1 AC Input Voltage Taps
The factory configured input voltage is shown in the serial tag label at the back of the power
source cabinet. If it is required to change the factory set input voltage configuration, a new EMI
filter and circuit breaker may have to be installed depending on what filter and breaker was
originally installed. Refer to the table below for input wiring configuration settings and EMI filter
and CB part numbers.
NOMINAL INPUT
VOLTAGE
TRANSFORMER
CONNECTIONS
CIRCUIT
BREAKER
EMI FILTER
208
(187 - 229)
Jumper 1, 5, 19, 23
100 amp
250558
Jumper 3, 7, 9, 13
Jumper 11, 15, 17, 21
270162
240
(216 - 264)
Jumper 1, 5, 20, 24
Jumper 4, 8, 9, 13
Jumper 12, 16, 17, 21
100 amp
270162
250558
380
(342 - 418)
Jumper 1, 22
Jumper 2, 5
Jumper 6, 9
Jumper 10, 13
50 amp
270175
250567
Jumper 14, 17
Jumper 18, 21
415
Jumper 1, 23
50 am
(374 - 456)
Jumper 3, 5
Jumper 7, 9
p
270175
250567
Jumper 11, 13
Jumper 15, 17
Jumper 19, 21
480
(432 - 528)
Jumper 1, 24
Jumper 4, 5
Jumper 8, 9
Jumper 12, 13
Jumper 16, 17
Jump
50 amp
270175
250567
er 20, 21
Table 3-1: AC Input transformer, EMI Filter and CB configurations.
Note: For 220V or 230V nominal input voltages, use the 240V nominal input tap setting.
California Instruments
30
Summary of Contents for FCS Series II
Page 4: ...User Manual Rev B FCS Series II California Instruments 4...
Page 27: ...User Manual Rev B FCS Series II California Instruments 27...
Page 89: ...FCS Series II 89 Figure 5 1 FCS System Block Diagram User Manual Rev B California Instruments...
Page 95: ...User Manual Rev B FCS Series II Figure 6 1 Calibration Setup California Instruments 95...