Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 30 / 174
Channel-oriented objects for shutter mode (continued):
Function:
Sun protection function (in shutter mode)
Object
Function
Name
Type
DP type
Flag
18, 44, … ,
200
4
Sunshine / shading
facade
Output ½ – 15/16
4
1 bit
1.002
C, W, -, (R)
1
Description:
1-bit object for activation or deactivation of sun shading in the simple or enlarged sun
protection mode (sun / no sun). The polarity can be parameterized.
Function:
Sun protection function (in shutter mode)
Object
Function
Name
Type
DP type
Flag
19, 45, … ,
201
4
Sunsh./shading
position
5
Output ½ – 15/16
4
1 byte
5.001
C, W, –, (R)
1
Description:
1-byte object for presetting a variable position value (0…255) for the height of the
blind/shutter curtain or the venting louver position when the sun protection is active.
Function:
Sun protection function (in shutter mode)
Object
Function
Name
Type
DP type
Flag
20, 46, … ,
202
4
Sunsh./shading slat
position
Output ½ – 15/16
4
1 byte
5.001
C, W, –, (R)
1
Description:
1-byte object for presetting a variable slat position value (0…255) when the sun
protection is active.
Function:
Sun protection function (in shutter mode)
Object
Function
Name
Type
DP type
Flag
21, 47, … ,
203
4
Sunshine slat
position offset
Output ½ – 15/16
4
1 byte
6.001
C, W, –, (R)
1
Description:
1-byte object for presetting a slat position angle (- 100 % … +100 % / smaller or larger
position angles are treated as + or – 100 %) for 'manual' readjustment of the slat position
during active sun protection.
Function:
Position feedback (in shutter mode)
Object
Function
Name
Type
DP type
Flag
23, 49, … ,
205
4
Position feedback
5
Output 1/2 – 15/16
4
1 byte
5.001
C, -, T, R
2
Description:
1-byte object for position feedback of the blind/shutter curtain height or louver position
(0…255)
5
The object designation varies with the type of curtain (blind, shutter / awning, venting louver).
4
The object designations are independent of the selected channel definition.
2
Depending on parameterization, feedback objects are either actively transmitting (T-flag set) or passively readable (R-flag set).
1
Each communication object can be read out. For reading, the R-flag must be set.