Description:
Values:
Remarks:
Ax – staircase function (x = number of output 1 … max. 16. / All outputs can be parameterized
independently / Only visible in switching mode and if parameter "Staircase function" under "Ax –
Enabled functions" is set to "enabled"!)
Staircase time
Hours (0...23)
0...23
This parameter is used for programming the
duration of the staircase lighting time.
Setting the staircase lighting time hours.
Minutes (0...59)
0…
3...59
Setting the staircase lighting time minutes.
Seconds (0...59)
0...59
Setting the staircase lighting time seconds.
Presetting:3 minutes
Staircase time retriggerable
?
yes
no
An active staircase lighting time can be
retriggered (setting "yes"). Alternatively,
retriggering can be excluded (setting "no").
Reaction to OFF telegram
switch off
ignore
An active staircase lighting time can be stopped
prematurely by deactivating the staircase
lighting time.
The staircase lighting time is stopped after
reception of an OFF-telegram to the "Staircase
function start/stop" object.
In the supplementary function "Time preset via
the bus" with the setting "Activate staircase
function via 'Staircase time' object ? = Yes", the
staircase lighting time can also be stopped
prematurely by inserting a factor of "0".
OFF-telegrams or factors of "0" will be ignored.
The staircase time will be executed completely.
Activate ON-delay for
staircase function ?
yes
no
The staircase function permits activating its own
ON-delay. This ON-delay function acts on the
trigger event of the staircase function and
therefore delays switching on.
The ON-delay is enabled.
The ON-delay is disabled.
The ON-delay parameterized under this item
is independent of the other time functions of
the actuator. It only acts on the staircase
function and not on the "Switching" object.