Description:
Values:
Remarks:
Manual control
Manual control in case of
bus voltage failure
disabled
enabled
This parameter can be used for programming
whether manual control is to be possible
(enabled) or deactivated in case of bus voltage
failure.
Manual control during bus
operation
disabled
enabled
This parameter can be used for programming
whether manual control is to be possible
(enabled) or deactivated during bus operation
(bus voltage on).
Disabling function ?
yes
no
Manual control can be disabled via the bus,
even if it is already active. For this purpose, the
disabling object can be enabled here.
Polarity of disabling object
0 = enabled; 1 = disabled
0 = disabled; 1 = enabled
This parameter defines the polarity of the
disabling object.
Only visible if the disabling function for
manual control is enabled.
Transmit status ?
yes
no
The current state of manual control can be
transmitted to the bus via a separate status
object, if bus voltage is available (setting: "yes").
Status object function and
polarity
0 = inactive; 1 = manual
control active
0 = inactive; 1 = permanent
manual control active
This parameter defines the information
contained in the status object. The object is
always "0", when the manual control mode is
deactivated.
The object is "1" when the manual control mode
is active (temporary or permanent).
The object is "1" only when the permanent
manual control is active.
This parameter is visible only if the manual
control status transmission is enabled.
The status will be actively transmitted to the
bus ("0") after bus voltage return only if a
manual control was terminated by such
return of voltage.