Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 126 / 174
Behaviour at the end of
permanent manual control
during bus operation
no change
output tracking
The behaviour of the actuator at the end of
permanent manual control depends on this
parameter.
All telegrams received during an active
permanent manual control mode for direct
operation (long-time/short-time, positioning,
scenes) are be rejected. After the end of the
permanent manual control mode, the current
state of all outputs remains unchanged. If,
however, a function with a higher priority is
being activated during manual control (safety,
forced position, sun protection), the actuator
activates the higher-ranking function for the
corresponding outputs.
During an active permanent manual control all
incoming telegrams (short-time telegrams
excepted) are internally tracked. At the end of
manual control, the outputs are adjusted
accordingly.
Disable bus control of
individual outputs during
bus operation?
yes
no
Individual outputs can be disabled locally during
permanent manual control so that the disabled
outputs can no longer be controlled via the bus.
Disabling by means of manual control is only
permitted if this parameter is set to "yes"