Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 134 / 174
Seconds (0...59)
0...
4…59
Sets the seconds of the slat moving time.
Presetting: 4 seconds
The moving time must be precisely
determined.
The slat moving time must be selected
shorter than the blind travelling time.
These parameters are visible only in the
'Blind' mode of operation.
Change-over time for travel
direction changes
0.5 s
1 s
2 s
5 s
Defines the break during a change of travel
direction (change-over time).
Description:
Values:
Remarks:
Ax – Enabled functions (x = number of output 1/2 … max. 15/16. / All outputs can be parameterized
independently / Only visible in shutter mode!)
Feedback functions
disabled
enabled
This parameter can be used to disable or to
enable the feedback functions. When the
function is enabled, the required parameters will
be displayed under "Ax –Feedbacks".
Safety functions
disabled
enabled
This parameter can be used disable or to
enable the safety functions. When the function
is enabled, the corresponding parameters will
be displayed under "Ax – safety" and the
necessary objects enabled.
Sun protection functions
disabled
enabled
This parameter can be used disable or to
enable the sun protection functions. When the
function is enabled, the corresponding
parameters will be displayed under "Ax - sun
protection" (3 parameter nodes) and the
necessary objects enabled.
Scene function
(only in ETS3.0d and
onwards)
disabled
enabled
This parameter can be used disable or to
enable the scene function. When the function is
enabled, the corresponding parameters will be
displayed under "Ax - scenes" and the
necessary object enabled.