2.4
Commissioning
After installation of the actuator and connection of the bus line, the mains supply and of all electrical loads,
the device can be put into operation. Only the shutter mode requires some special commissioning
measures before the device can programmed with the ETS. The following procedure is generally
recommended...
DANGER!
Electric shock in case of accidental contact with live parts. Electric shocks can be fatal.
Before working on the device, cut out the mains supply and cover up live parts in the
surroundings.
Measuring the travelling times (only in shutter mode)
For the purpose of positioning blinds, shutters and awnings or for adjusting the opening angle of venting
louvers, the actuator needs accurate information about the maximum travelling time.
Switch on the mains supply.
If not yet done, move the blind/shutter into the upper end position (open venting louver completely)
The upper limit-stop position is reached (venting louver opened).
Start the measuring time and move the blind/shutter by manual control into the lower end position (close
the venting louver completely).
Stop the time measurement when the lower limit (when the completely closed) position is reached.
Enter the measured value in the ETS (cf. software description).
It is recommended to perform several time measurements and to take the average of these values.
The travelling time can also be determined after commissioning with the ETS (bus operation).