Channel-oriented objects for switching mode (continued):
Function:
Switching status feedback (in switching mode)
Object
Function
Name
Type
DP type
Flag
18, 31, … ,
213
3
Switching feedback
Output 1 – 16
3
1 bit
1.001
C, -, T, R
2
Description:
1-bit object for feedback signalling of the switching state of an output
("1" = on / "0" = off; observe the parameterized mode of operation!)
Channel-oriented objects for shutter mode:
Function:
Long-time operation (in shutter mode)
Object
Function
Name
Type
DP type
Flag
10, 36, … ,
192
4
Long-time operation Output 1/2 –
15/16
4
1 bit
1.008
C, W, -, (R)
1
Description:
1-bit object for activation of the long-time operation
Function:
Short-time operation (in shutter mode)
Object
Function
Name
Type
DP type
Flag
11, 37, … ,
193
4
Short-time operation Output 1/2 –
15/16
4
1 bit
1.007
C, W, –, (R)
1
Description:
1-bit object for activation of the short-time operation or for stopping of a travel movement.
Function:
Forced position (in shutter mode - only for ETS3.0d and onwards)
Object
Function
Name
Type
DP type
Flag
12, 38, … ,
194
4
Forced position
Output 1/2 –
15/16
4
2 bit
2.008
C, W, –, (R)
1
Description:
2-bit object for forced control of an output. The object state after bus voltage return can
be predefined by means of a parameter.
Function:
Scene function (in shutter mode - only for ETS3.0d and onwards)
Object
Function
Name
Type
DP type
Flag
13, 39, … ,
195
4
Scene extension
Output 1/2 –
15/16
4
1 byte
18.001
C, W, –, (R)
1
Description:
1-byte object for recalling scenes or for storing new scene values.
3
The number of outputs of the communication objects depends on the programmed device.
2
Depending on parameterization, feedback objects are either actively transmitting (T-flag set) or passively readable (R-flag set).
4
The object designations are independent of the selected channel definition.
1