Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 18 / 174
Controlling an output manually
Manual control (permanent or temporary) is active.
Select the desired output: Press the key briefly (if necessary, repeatedly).
The state indicator LED of the selected output A1...A8 / A16 is flashing. In the shutter mode, the LEDs of
an output combination are flashing. In addition, the switching state or a travel movement of the selected
output is signalled by the status LED "ON/ " or "OFF/ " on the keypad.
Control the output by pressing the ON/ or the OFF/ key.
In shutter mode:
Brief press (< 1 s) on the ON/ or OFF/ key: stopping.
Long press (> 1 s) on the ON/ key: upward movement or stopping.
Long press (> 1 s) on the OFF/ key: downward movement or closing.
In switching mode:
Pressing the ON/ key: switching on (closing the relay contact).
Pressing the OFF/ key: switching off (opening the relay contact).
The selected drive motor executes the corresponding commands immediately.
Shutting off all outputs (in shutter mode: stopping all drives)
Permanent manual control is active:
Press the ALL OFF key.
All outputs are shut off immediately (stop). The outputs are not locked. Individual activation is again
possible after shutoff.
The "ALL-OFF" function is not available in temporary manual control.
Disabling bus control of individual outputs manually
Permanent manual control is active:
Disabling of the bus control mode must have been enabled in the ETS.
Select the output: Press the key briefly (if necessary, repeatedly).
The state indicator LEDs of the selected output A1...A8 / A16 are flashing. In the blind/shutter mode, the
LEDs of the output combination are flashing. In addition, the switching state or a travel movement of the
selected output is signalled by the status LED "ON/ " or "OFF/ " on the keypad.
Press the and the key simultaneously for at least 5 s.
The concerned output A1...A8 / A16 is locked (control via the bus not possible).
The state indicator LEDs of the selected output A1...A8 / A16 are flashing fast.
To unlock, proceed in the same way.
An output that has been disabled manually can thereafter only be operated in the permanent manual
mode.