Scene function (only in ETS 3.0d and onwards)
Up to 8 scenes can be generated and the corresponding scene values stored in the actuator separately for
each output in switching mode (only in ETS 3.0d and onwards). The scene values are recalled or stored via
a separate scene extension object by means of extension telegrams. The datapoint type of the extension
object permits addressing of up to 64 scenes max. For this reason, the scene number (1...64) with which
the internal scene (1...8) is addressed can be determined in the parameterization of a scene.
The scene function must have been enabled on parameter page "Ax – Enabled functions" separately for
each output before the required communication objects and parameters (on parameter page "Ax – scenes")
are visible.
The scene function can be combined with other functions of the output (cf. Fig. 18) with the command last
received or selected always being executed:
A telegram to the "Switching" object or a scene recall or a scene storage telegram during an active
staircase function ends the staircase lighting time prematurely and sets the output to the switching state
corresponding to the object value (time delays taken into account) or the scene value received. similarly, the
output switching state set by the "Switching" object or a scene recall can be overridden by a staircase
function or by the result of a logic function.
A combination of the function with cyclical monitoring is not possible.
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
ON-delay
pre-warning
function
Object
"staircase function
start/stop"
staircase
function
(time-controlled)
* = parameterizable as an option
relay
disabling or
forced-control
position
function
mode of
operation
responde to
- bus voltage failure
- bus voltage return
- ETS programming
blinking
(disabling function only)
logic
operation
recall
store
scene
function
Objekt
"switching"
central object polarity
time delays
Object
"Centralized switch."
Note: logic operation function only as an alternative
to staircase lighting timer function
cyclical
transmission
delay after
bus voltage return
cyclical
transmission
delay after
bus voltage return
Object
"logic operation"
Object
"
switching feedback
"
Object
"centralized feedb."
Object
"scene extension"
Fig. 18: Functional diagram of the scene function