Switch/shutter actuator 8/4gang 16A RMD
75318003
Switch/shutter actuator 16/8gang 16A
RMD
75310002
Technical
Documentation
© Berker GmbH & Co KG 2007
Version: 04.04.2007
Part 5
(Subject to prior change)
75310002.doc
Seite: 170 / 174
Description:
Values:
Remarks:
Ax – supplementary functions (x = number of output 1 … max. 16. / All outputs can be parameterized
independently / Only visible in switching mode!)
Selection of supplementary
function
no supplementary
function
disabling function
forced-control position
This parameter can be used to define and to
enable the supplementary function. - The
disabling function can only be parameterized as
an alternative to the forced-control position
function.
The forced-control position function is only
parameterizable in the ETS3.0d and
onwards!
Polarity of disable object
0 = enabled;
1 = disabled
1 = enabled;
0 = disabled
This parameter defines the polarity of the
disabling object.
After bus voltage return or programming of
the application or of the parameters with the
ETS, the disabling function is always
deactivated (object value "0"). - In the
inverted setting ("1 = enabled; 0 = disabled"),
a "0" telegram update must first be sent after
the initialization before the disabled state can
be activated.
Behaviour at the beginning
of the disabling function
no change of switching
state
switching off
switching on
blinking
The behaviour of the output at the beginning of
the disabling function can be parameterized.
At the beginning of the disabling function, the
relay of the output shows no reaction and
remains in the current switching state. -
Thereafter, the output is locked.
The output switches off at the beginning of the
disabling function and goes into lock.
The output switches on at the beginning of the
disabling function and goes into lock.
The output blinks on and off during disabling
and is locked during this time. The blinking time
is generally parameterized for all outputs under
"General". During blinking, the logic switching
state is "ON - 1".
An output disabled via the bus can still be
operated by hand!
This parameter is only visible, if the
parameter "Selection of supplementary
function is set to "disabling function".