Set the parameter "Behaviour at the beginning of the disabling function" on parameter page "Ax –
supplementary functions" to the desired behaviour.
At the beginning of disabling, the parameterized behaviour will be executed and the output locked. -
When the setting "No change of switching state" is selected, the relay of the output shows no reaction
and remains in the switching state last set (switching state in acc. with last non-inverted feedback
telegram). When the setting "Blinking" is selected, the output is switched on and off cyclically during
disabling. The blinking time is generally parameterized for all outputs on the "General" parameter page.
During blinking, the logic switching state is "ON - 1".
Set the parameter "Behaviour at the end of the disabling function" on parameter page "Ax –
supplementary functions" to the desired behaviour.
At the end of disabling, the parameterized behaviour will be executed and the output re-enabled. - When
the setting "No change of switching state" is selected, the relay of the output shows no reaction and
remains in the state last set by the disabling function.
When the setting "Setting tracked state" is selected, the last switching state existing before the disabling
function or the switching state internally tracked during the disabling function will be set. In this case,
residual times of time functions or of the staircase functions will be tracked as well, if they have not
completely elapsed at the time of re-enabling the disabling function. In the settings "No change of
switching state", "Switching on", "Switching off" or "Blinking", the states set at the end of the disabling
function have no influence on time or staircase functions
When the setting "Blinking" is selected, the output is switched on and off cyclically after disabling.
Blinking persists until a new switching state is set. The blinking time is generally parameterized for all
outputs on the "General" parameter page. During blinking, the logic switching state is "ON - 1".
The states defined for the end of the disabling function override a logic function if parameterized. The
parameterized logic operation will be executed and the result forced on the output only if at least one
input state of the logic operation changes or is updated after the disabling state has been suspended.