Time delay for feedback
after bus voltage return ?
yes (delay time under
"General")
no
The feedback telegram can be transmitted to
the bus with a delay after bus voltage return or
after programming with the ETS. setting "yes"
activates the feedback delay in case of bus
voltage return. The delay time is parameterized
under "General".
This parameter is only visible in case of an
actively transmitting feedback object.
Invalid blind position
feedback
no feedback
feedback object is active
signalling object
feedback object is passive
status object
The actuator can report to the bus that the
current blind position is unknown (e.g. after an
initialization, when no reference travel has been
executed as yet).
No feedback object available for the output.
Feedback deactivated.
Feedback and object are activated. The object
transmits actively (telegram transmission after
change).
Feedback and object are activated. The object
is passive (telegram transmission only as a
response to 'Read' request.
The communication flags of the object are
automatically set by the ETS according to the
setting.
This parameter is visible only in the 'Blind'
mode of operation.
Invalid shutter/awning
position feedback
no feedback
feedback object is active
signalling object
feedback object is passive
status object
The actuator can report to the bus that the
current shutter/awning position is unknown (e.g.
after an initialization, when no reference travel
has been executed as yet).
No feedback object available for the output.
Feedback deactivated.
Feedback and object are activated. The object
transmits actively (telegram transmission after
change).
Feedback and object are activated. The object
is passive (telegram transmission only as a
response to 'Read' request.
The communication flags of the object are
automatically set by the ETS according to the
setting.
This parameter is visible only in the
'Shutter/awning' mode of operation.