2.5
First start-up
NOTE
Before starting up the unit for the first time, check that the connected
motor is suitable for the respective device variant (see chapter 6.1) and
that the controller has been wired correctly (see chapter 2.4).
For starting up via the front panel, the minimum wiring requirements for
the signal interface must be observed (see chapter 2.4.3).
ATTENTION
The mains power supply and the 24 V supply voltage of the unit
must be switched off.
1.
Set the mains voltage to 115 V or 230 V with the selector switch
on the unit top.
ATTENTION
The setting must correspond to the actual mains voltage available.
2.
Switch on the power supply for the power controller.
3.
Switch on the 24 V supply voltage for the processor unit. (Mains
voltage and 24 V supply voltage may also be switched on
simultaneously.)
→
The controller executes a self-test during which the numbers
0, 1, 2, 3 appear in the status display, followed by the software
version number.
→
Subsequently, the parameter “P00” is displayed.
NOTE
The P00 parameter can be used for setting the operating mode for the
controller (see chapter 3.3.1).
4.
Use the keys to set the following motor parameters:
P01 =
Motor phase current (in A) according to the motor type
plate
ATTENTION
The set phase current must be equal to or less than the nominal
phase current specified on the motor type plate (the lower the set
phase current, the lower the motor torque).
P20 = 2
Activate rotation monitoring if an encoder is installed on
the motor.
NOTE
Operation via front panel and setting of other parameters is described in
chapter 3.3.
5.
Completing the parameter setting process:
Select the “End” option and confirm by pressing
.
→
The “run” message is displayed.
Switching ON
Self-test
V
e
rsion no.
230V
Installation
2-24
WDP3-01X Ident. no.: 00441109760