2.4.1
Mains connection
1.
Set the 115 V or 230 V mains voltage on the selector switch at the
unit top.
ATTENTION
The setting must correspond to the actual mains voltage available.
2.
Mount wire end ferrules on the device end of the mains power
cable.
3.
Fasten three litz wires (fig. 2-5) with screws:
L
Phase (115 VAC or 230 VAC)
N
Neutral
PE
Protective conductor
NOTE
A mains filter can be inserted in order to shield the unit against inter-
ference (see chapter 6.2.2).
→
→
→
L
N
PE
Fig. 2-5 Mains connection –
device end
230V
Installation
WDP3-01X Ident. no.: 00441109760
2-7