3.6.5 5AC901.BUPS-01
3.6.5.1 General information
•
Battery unit for UPS IF option 5AC901.IUPS-01
•
Maintenance-free lead acid battery
•
2 Panasonic 12 V 2.2 Ah rechargeable batteries connected in series
•
Rated voltage 24 V
•
Capacity 2.2 Ah
The battery unit is subject to wear and should be replaced regularly (after the specified service life at the latest).
Warning!
Battery unit 5AC901.BUPS-01 is only permitted to be operated with UPS IF option 5AC901.IUPS-01!
3.6.5.2 Order data
Model number
Short description
Figure
Uninterruptible power supplies
5AC901.BUPS-01
Battery unit 2.2 Ah - For UPS 5AC901.IUPS-01
Required accessories
Uninterruptible power supplies
5CAUPS.0005-01
UPS cable - 0.5 m - For 5AC901.IUPS-xx
5CAUPS.0010-01
UPS cable - 1 m - For 5AC901.IUPS-xx
5CAUPS.0030-01
UPS cable - 3 m - For 5AC901.IUPS-xx
Table 112: 5AC901.BUPS-01 - Order data
3.6.5.3 Technical data
Information:
The following specifications, properties and limit values apply only to this accessory and may deviate
from those that apply to the complete system. For the complete system in which this accessory is
installed, for example, the data specified for that complete system applies.
Model number
5AC901.BUPS-01
General information
Battery
Type
Panasonic 12 V 2.2 Ah; two rechargeable batteries connected in series
Service life
Up to 5 years at 20°C
1)
Design
Maintenance-free lead acid battery
Temperature sensor
NTC resistance
Maintenance interval during storage
Charge 1 time every 6 months
Certifications
CE
Yes
UL
cULus E115267
Industrial control equipment
HazLoc
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T3C
2)
GOST-R
Yes
Charge duration when battery low
Typ. 5 hours
Electrical characteristics
Nominal voltage
24 V
Capacity
2.2 Ah
Fuse
Yes
Battery charging data
Charging current
3)
Typ. 0.88 A
Operating conditions
Pollution degree per EN 61131-2
Pollution degree 2
Table 113: 5AC901.BUPS-01 - Technical data