Technical data • Complete system
18
Automation PC 3100 user's manual V0.60
2.1.2 DVI operation
In the DVI operating mode, all signals needed to operate the Automation Panel are each transferred over a separate
cable. The brightness of the display can be set using the brightness buttons.
2.1.2.1 DVI operation with single-touch Automation Panel
If an Automation Panel with resistive touch screen (single-touch) is operated with DVI, then a DVI cable, USB type
A/B cable and RS232 cable must be connected.
Single-touch Automation Panel
with SDL/DVI receiver
USB type A/B cable
DVI mode, single-touch
RS232 cable
DVI cable
Industrial PC
Power supply
Grounding
Power supply
Grounding
Availability of interfaces on the Automation Panel with SDL/DVI receiver:
Panel In
✓
USB In
✓
USB 2.0
Power supply
✓
Brightness controls
✓
USB1, USB2
✓
USB 2.0
COM touch screen inter-
face
✓
Grounding
✓
Maximum cable length: 5 m
Requirements
•
Automation Panel with SDL/DVI receiver
•
B&R industrial PC with DVI interface
•
DVI cable, USB type A/B cable, RS232 cable
2.1.2.2 DVI mode with multi-touch Automation Panel
If an Automation Panel with PCT touch screen (multi-touch) is operated with DVI, then a DVI cable and USB type
A/B cable must be connected.
DVI cable
USB type A/B cable
Multi-touch Automation Panel
with SDL/DVI receiver
DVI mode, multi-touch
Industrial PC
Power supply
Grounding
Power supply
Grounding
Availability of interfaces on the Automation Panel with SDL/DVI receiver:
Panel In
✓
USB In
✓
USB 2.0
Power supply
✓
Brightness controls
✓
USB1, USB2
✓
USB 2.0
COM touch screen inter-
face
x
Grounding
✓
Maximum cable length: 5 m
Requirements
•
Automation Panel with SDL/DVI receiver
•
B&R industrial PC with DVI interface
•
DVI cable, USB type A/B cable