Technical data • Complete system
Chapter 2
Technical data
Automation PC 3100 user's manual V0.60
23
2.3 Environmental characteristics
2.3.1 Temperature specifications
Since the various system units can be combined with a monitor/panel option and interface option, the following
tables provide an overview for determining the maximum, minimum and typical ambient temperatures possible
based on these components.
Information:
The minimum and maximum specified ambient temperatures have been calculated for operation un-
der worst-case conditions. Experience has shown that higher ambient temperatures can be achieved
in typical applications, e.g. in Microsoft Windows. Testing and evaluation in this regard must be per-
formed on-site by the user in each individual case (temperatures can be read in BIOS or using the B&R
Control Center, for example).
Information regarding worst-case conditions
•
Thermal Analysis Tool (TAT V5) from Intel for simulating 100% processor load (100% workload, 100%
memory)
•
BurnInTest tool (BurnInTest V7.1 Pro from PassMark Software) for simulating a 100% gigabit network load.
•
4x 1 A USB load
•
Maximum system expansion and power consumption
2.3.1.1 Maximum ambient temperature for worst-case operation
All values apply to non-condensing operation.
C-3965U
2.2 GHz
i3-7100U
2.4 GHz
i5-7300U
2.6 GHz
i7-7600U
2.8 GHz
All temperature values in degrees
Celsius (°C) at 500 m above sea level, non-condensing.
The maximum ambient temperature is typically derated by
1°C per 1000 meters starting at 500 meters above sea level.
5APC3100.KBUO-000
5APC3100.KBU1-000
5APC3100.KBU2-000
5APC3100.KBU3-000
Maximum ambient temperature for worst-case operation
60
55
50
50
What else can also be operated at the max.
ambient temperature, or is there a limitation?
5CFAST.xxxx-00 ≥E0
✓
✓
✓
✓
CFast cards
5CFAST.xxxx-10
✓
✓
✓
✓
5ACCLI02.DPO0-000
✓
✓
✓
✓
5ACCLI02.SDL0-000
✓
✓
✓
✓
Graphics options
5ACCLI02.SD40-000
55
✓
✓
✓
5AC901.I485-00
✓
✓
✓
✓
5AC901.ICAN-00
✓
✓
✓
✓
5AC901.ICAN-01
✓
✓
✓
✓
5AC901.IHDA-00
✓
✓
✓
✓
5AC901.IRDY-00
✓
✓
✓
✓
5AC901.IPLK-00
✓
✓
✓
✓
5AC901.ISIO-00
✓
✓
✓
✓
5AC901.ISRM-00
✓
✓
✓
✓
Interface options
5AC901.IETH-00
✓
✓
✓
✓
Table 5: Ambient temperature during operation
2.3.1.2 Minimum ambient temperature for worst-case operation
The minimum ambient temperature for non-condensing operation is 0°C.